PRPL202201143
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Plumbing Rough-in Inspection | Partial Pass | 4/13/2022 (12:30 - 2:30) | 4/13/2022 (PM) | 04/13/2022 |
Miscellaneous/Other
Comment Only
04/13/2022
Air tests on 2 groups of under ground plumbing
|
||||
Plumbing Rough-in Inspection | Partial Pass | 4/18/2022 (8:00 - 10:00) | 4/18/2022 (AM) | 04/18/2022 |
Miscellaneous/Other
Comment Only
04/18/2022
5 lb. Air test on underground bathroom groups on northwest side of building.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 4/20/2022 (8:00 - 10:00) | 4/20/2022 (AM) | 04/20/2022 |
Miscellaneous/Other
Comment Only
04/20/2022
5 lb. Air test on underground on north bath and branches, 5 lb. Air test on east underground bathrooms, and manometer on flammable waste interceptor. Okay to cover. Will schedule inspection for demo of remaining existing underground.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 4/25/2022 (12:30 - 2:30) | 4/25/2022 (PM) | 04/25/2022 |
Plumbing Rough-in Inspection | Partial Pass | 5/10/2022 (8:00 - 10:00) | 5/10/2022 (AM) | 05/10/2022 |
Miscellaneous/Other
Comment Only
05/10/2022
All waste and vent air tested on north side. Ok to cover
|
||||
Plumbing Rough-in Inspection | Passed | 5/13/2022 (8:00 - 10:00) | 5/13/2022 (AM) | 05/13/2022 |
Miscellaneous/Other
Comment Only
05/13/2022
Air test on south side
|
||||
Plumbing Final Inspection | Partial Pass | 10/13/2022 (8:00 - 10:00) | 10/13/2022 (AM) | 10/13/2022 |
Miscellaneous/Other
Comment Only
10/13/2022
5 manometer tests
Visual on mechanical
Visual on all fixtures but 2 sinks waiting for counter tops
Dap one toilet
Fix leak on mixer under lav
Repair and test RPZ
|
||||
Plumbing Final Inspection | Passed | 12/9/2022 (10:00 - 12:00) | 12/9/2022 (AM) | 12/09/2022 |
Miscellaneous/Other
Comment Only
12/09/2022
Sink installations in Steinway room and break room completed.
Final final
Water heater install too high in ceiling for replacement, maintenance, or emergency without a lift or maybe 12 foot ladder
Plumber may not have had a choice as to the elevation of the water heater.
|