Permit Application Status

PRAL201704062


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRAL201704062
Fire Alarm
Finaled
MOAC MALL HOLDINGS LLC
Alteration/Remodel
Fire alarm system for Xscape MOA
05/23/2017
05/24/2017
10/30/2021
06/23/2017

Locations

Permits

Permit Number: PRAL201704062

Fire Alarm
Finaled
05/24/2017
10/30/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Acceptance Test Inspection Failed 5/26/2017 (7:00 - 8:00) 5/26/2017 05/26/2017
Corrections:


Miscellaneous/Other
Carried Forward
05/26/2017
Notification appliances didn't operator properly. Smoke detector blocked by overhead garage door feature. Need to test during normal arcade operations to ensure notification (horns) meet/exceed the ambient noise requirements.

Acceptance Test Inspection Passed w/ Conditions 5/30/2017 (7:00 - 8:00) 5/30/2017 05/30/2017
Corrections:


Miscellaneous/Other
Resolved
05/30/2017
Notification appliances didn't operator properly. Smoke detector blocked by overhead garage door feature.

Miscellaneous/Other
Outstanding
05/30/2017
Need to test during normal arcade operations to ensure notification (horns) meet/exceed the ambient noise requirements.

Fire Inspection Final Passed w/ Conditions 06/02/2017
Corrections:


Miscellaneous/Other
Outstanding
06/02/2017
Need to retest with games installed to verify notification level is 15 decibels above ambient noise.

Fire Inspection Final Not Ready 6/5/2017 (7:00 - 8:00) 6/5/2017 06/05/2017
Fire Inspection Final Failed 6/6/2017 (7:00 - 8:00) 6/6/2017 06/06/2017
Corrections:


Inadequate fire alarm coverage.
Carried Forward
06/06/2017
Inadequate fire alarm coverage. Speakers at 8 over ambient.

Fire Inspection Final Not Ready 6/20/2017 (7:00 - 8:00) 6/20/2017 06/22/2017
Corrections:


Inadequate fire alarm coverage.
Carried Forward
06/22/2017
Inadequate fire alarm coverage. Speakers at 8 over ambient.

Fire Inspection Final Passed 6/23/2017 (7:00 - 8:00) 6/23/2017 06/23/2017
Fire Inspection Final Passed 06/23/2017
Corrections:


Inadequate fire alarm coverage.
Resolved
06/23/2017
Inadequate fire alarm coverage. Speakers at 8 over ambient.