Summary

PRAL201903083
Fire Alarm
Expired
MSP BLOOMINGTON LLC
Other
New fire alarm install. (Whirly Ball) (FACP, AMP, Annunciator, pull stations, monitors etc)
04/08/2019
05/06/2019
01/21/2020

Locations

Permits

Permit Number: PRAL201903083

Fire Alarm
Expired
05/06/2019
01/21/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Inspection Final Pending
Acceptance Test Inspection Failed 7/22/2019 (8:00 - 10:00) 7/22/2019 (AM) 07/22/2019
Corrections:


Miscellaneous/Other
Outstanding
07/22/2019
Need to add notification appliances under mezzanine in laser tag gaming area. Remove plastic coverings off of all notification appliances. Found several throughout. Need to test live ride and music shutdown.

Fire Inspection Final Failed 7/22/2019 (8:00 - 10:00) 7/22/2019 (AM) 07/22/2019
Corrections:


Miscellaneous/Other
Carried Forward
07/22/2019
Need to add notification appliances under mezzanine in laser tag gaming area. Remove plastic coverings off of all notification appliances. Found several throughout. Need to test live ride and music shutdown.

Acceptance Test Inspection Passed 7/25/2019 (2:30 - 3:30) 7/25/2019 (PM) 07/25/2019
Corrections:


Miscellaneous/Other
Resolved
07/25/2019
Need to add notification appliances under mezzanine in laser tag gaming area. Remove plastic coverings off of all notification appliances. Found several throughout. Need to test live ride and music shutdown.

Fire Inspection Final Partial Pass 7/25/2019 (12:30 - 2:30) 7/25/2019 (PM) 07/25/2019
Corrections:


Miscellaneous/Other
Outstanding
07/25/2019
Need to add notification appliances under mezzanine in laser tag gaming area.

Miscellaneous/Other
Comment Only
07/25/2019
Partial final approved. Need to test laser tag game area prior to occupancy