PRAL201907021
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Fire Rough-in Inspection | Partial Pass | 12/12/2019 (8:00 - 10:00) | 12/12/2019 (AM) | 12/12/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/12/2019
Partial final. Water flow alarms and tamper valves tested and approved on floors 2-5.
|
||||
Acceptance Test Inspection | Failed | 1/22/2020 (10:00 - 12:00) | 1/22/2020 (AM) | 01/23/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
01/23/2020
Ansul system tamper and flow needs to be tested to ensure it reports to panel.
Fire alarm Notification in boardroom
Linen chute door needs to close and latch in laundry room. Need to retest mag hold open.
CO detection needed in rooms with gas fired appliances.
Reduce dB of notifications appliances throughout had readings over 120.
Southeast 1st pull station needs to be reprogrammed-relabeled.
|
||||
Acceptance Test Inspection | Failed | 01/23/2020 | ||
Corrections:
Miscellaneous/Other
Carried Forward
01/23/2020
Ansul system tamper and flow needs to be tested to ensure it reports to panel.
Fire alarm Notification in boardroom
Linen chute door needs to close and latch in laundry room. Need to retest mag hold open.
CO detection needed in rooms with gas fired appliances.
Reduce dB of notifications appliances throughout Got readings over 120.
Southeast 1st pull station needs to be reprogrammed-relabeled.
|
||||
Fire Inspection Final | Failed | 1/22/2020 (10:00 - 12:00) | 1/22/2020 (AM) | 01/23/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
01/23/2020
Ansul system tamper and flow needs to be tested to ensure it reports to panel.
Fire alarm Notification in boardroom
Linen chute door needs to close and latch in laundry room. Need to retest mag hold open.
CO detection needed in rooms with gas fired appliances.
Reduce dB of notifications appliances throughout Got readings over 120.
Southeast 1st pull station needs to be reprogrammed-relabeled.
|
||||
Acceptance Test Inspection | Passed | 01/24/2020 | ||
Corrections:
Miscellaneous/Other
Outstanding
01/23/2020
Ansul system tamper and flow needs to be tested to ensure it reports to panel.
Fire alarm Notification in boardroom
Linen chute door needs to close and latch in laundry room. Need to retest mag hold open.
CO detection needed in rooms with gas fired appliances.
Reduce dB of notifications appliances throughout Got readings over 120.
Southeast 1st pull station needs to be reprogrammed-relabeled.
|
||||
Fire Inspection Final | Passed | 01/24/2020 | ||
Corrections:
Miscellaneous/Other
Resolved
01/24/2020
Ansul system tamper and flow needs to be tested to ensure it reports to panel.
Fire alarm Notification in boardroom
Linen chute door needs to close and latch in laundry room. Need to retest mag hold open.
CO detection needed in rooms with gas fired appliances.
Reduce dB of notifications appliances throughout Got readings over 120.
Southeast 1st pull station needs to be reprogrammed-relabeled.
|