PRAL201910736
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Fire Inspection Final | Partial Pass | 10/17/2019 (12:30 - 2:30) | 10/17/2019 (PM) | 10/17/2019 |
|
Corrections:
Miscellaneous/Other
Comment Only
10/17/2019
Functionality of horn strobes, pull station, and smoke detector over FACP OK. Monitoring tested OK. Area or refuge and duct detectors are not in place so they could not be tested.
|
||||
| Fire Inspection Final | Failed | 12/2/2019 (10:00 - 12:00) | 12/2/2019 (AM) | 12/03/2019 |
|
Corrections:
Inadequate fire alarm coverage.
Carried Forward
12/04/2019
Inadequate fire alarm coverage. Add/relocated notification appliances as needed on 2nd and 3rd floor.
Found areas in storage locker hallways that are lacking notification appliances. Contract to add/relocated devices as needed and call for a reinspection.
|
||||
| Fire Inspection Final | Passed | 12/5/2019 (8:00 - 10:00) | 12/5/2019 (AM) | 12/05/2019 |
|
Corrections:
Inadequate fire alarm coverage.
Outstanding
12/04/2019
Inadequate fire alarm coverage. Add/relocated notification appliances as needed on 2nd and 3rd floor.
Found areas in storage locker hallways that are lacking notification appliances. Contract to add/relocated devices as needed and call for a reinspection.
|
||||