PRAL201911563
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Fire Inspection Final | Pending | |||
Fire Inspection Final | Failed | 10/3/2019 (8:00 - 10:00) | 10/3/2019 (AM) | 10/03/2019 |
Acceptance Test Inspection | Failed | 10/3/2019 (7:00 - 8:00) | 10/3/2019 (AM) | 10/03/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
10/03/2019
Pretest all devices to ensure proper address and function. Found several not programmed correctly at time of inspection.
Provide fire alarm sequence of operations to including information on smoke detector activation.
No corridor and/or lobby area smoke detectors shall be delayed in sounding a general fire evacuation signal.
Provide a Fire Alarm Annunciation Panel at the main vestibule.
Pre-test to ensure fire roll down doors operate on all general fire evacuation signals.
Please note: in the future if work is performed prior to approved City of Bloomington Permit contractor will be doubled feed. Permit application for this scope of work was applied for at the last minuet.
|
||||
Fire Inspection Final | Partial Pass | 10/7/2019 (10:00 - 12:00) | 10/7/2019 (AM) | 10/08/2019 |
Acceptance Test Inspection | Partial Pass | 10/7/2019 (10:00 - 12:00) | 10/7/2019 (AM) | 10/08/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
10/08/2019
Pretest all devices to ensure proper address and function. Found several not programmed correctly at time of inspection.
Provide fire alarm sequence of operations to including information on smoke detector activation.
No corridor and/or lobby area smoke detectors shall be delayed in sounding a general fire evacuation signal.
Provide a Fire Alarm Annunciation Panel at the main vestibule.
Pre-test to ensure fire roll down doors operate on all general fire evacuation signals.
Please note: in the future if work is performed prior to approved City of Bloomington Permit contractor will be doubled feed. Permit application for this scope of work was applied for at the last minuet.
|
||||
Acceptance Test Inspection | Passed | 2/14/2020 (7:00 - 8:00) | 2/14/2020 (AM) | 02/14/2020 |
Corrections:
Miscellaneous/Other
Outstanding
10/08/2019
Pretest all devices to ensure proper address and function. Found several not programmed correctly at time of inspection.
Provide fire alarm sequence of operations to including information on smoke detector activation.
No corridor and/or lobby area smoke detectors shall be delayed in sounding a general fire evacuation signal.
Provide a Fire Alarm Annunciation Panel at the main vestibule.
Pre-test to ensure fire roll down doors operate on all general fire evacuation signals.
Please note: in the future if work is performed prior to approved City of Bloomington Permit contractor will be doubled feed. Permit application for this scope of work was applied for at the last minuet.
|