Permit Application Status

PRAL202312314


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRAL202312314
Fire Alarm
Finaled
8800 QUEEN LLC
Alteration/Repair/Replace
Severe weather notification installation: • (13) AMT-24MCW-FR Notification devices, each device has (3) inputs which can be used to trigger (3) isolated selectable signals. Each signal has a selectable hi and low output for selectable signal notification volume. • (1) HPF-PS10 Power Supply used to trigger up to (7) independently power limited output circuits. This power supply will power the newly installed FCM-1 modules, the FCM-1 modules will then switch power to each circuit of the notification devices depending on the emergency event that is occurring. The power supply will be installed next to the existing fire alarm panel. • (1) FMM-1 Monitor Module which will monitor the fault state of the power supply • (3) FCM-1 Control Modules which will trigger each of the (3) notification signals, depending on the emergency event that is occurring
10/06/2023
10/20/2023
06/25/2024
12/28/2023

Locations

Permits

Permit Number: PRAL202312314

Fire Alarm
Finaled
10/20/2023
06/25/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Inspection Final Passed 12/28/2023 (8:00 - 10:00) 12/28/2023 (AM) 12/28/2023
Weather alert/fire alarm transition tested ok.