Summary

PRAL202411195
Fire Alarm
Finaled
8800 QUEEN LLC
Alteration/Repair/Replace
436847.General Dynamics SAPF Phase 1.01-24 • Reinstall (2) Speaker/strobe ceiling mount notification devices • Furnish (17) Speaker/strobe wall mount notification devices with back boxes • Furnish (8) Strobe only wall mount notification devices with back boxes • Installation & Programming
08/23/2024
09/06/2024
09/20/2025
03/24/2025

Locations

Permits

Permit Number: PRAL202411195

Fire Alarm
Finaled
09/06/2024
09/20/2025

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Inspection Final Failed 1/31/2025 (7:00 - 8:00) 1/31/2025 (AM) 01/31/2025
Fire Inspection Final Partial Pass 2/18/2025 (8:00 - 10:00) 2/18/2025 (AM) 02/19/2025
HVAC damper did not function upon activation of the server room suppression system.
Fire Inspection Final Passed 02/24/2025