PRBD201706017
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Passed w/ Conditions | 8/29/2017 (8:00 - 10:00) | 8/29/2017 | 08/29/2017 |
Corrections:
Miscellaneous/Other
Outstanding
08/29/2017
Framing - A) patch 2 hr - 2 layer gypsum wall of tenant side of 2 hr rated stairwell. B) All exit signage and emergency lighting must be on emergency generator circuit. C) plumbing, hvac, electrical, low voltage, fire sprinkler above ceiling inspections required.
|
||||
Above Ceiling Inspection | Passed | 10/19/2017 | ||
Electrical, low voltage, plumbing,mechanical, firesprinkler above ceiling required. Exit signage to be on emergency generator circuits. | ||||
Fire Inspection Final | Not Ready | 10/19/2017 (10:00 - 12:00) | 10/19/2017 | 10/19/2017 |
Corrections:
Provide additional exits
Carried Forward
10/19/2017
Provide additional exits
|
||||
Building Final Inspection | Passed w/ Conditions | 10/19/2017 (10:00 - 12:00) | 10/19/2017 | 10/19/2017 |
Corrections:
Miscellaneous/Other
Outstanding
10/19/2017
Final approved, contingent upon fire marshal final for adding and removing exit signs, and proper function of adjoining suite card reader, and plumbing final on break room sink.
|
||||
Fire Inspection Final | Passed | 10/25/2017 (8:00 - 10:00) | 10/25/2017 | 10/25/2017 |
Corrections:
Provide additional exits
Outstanding
10/19/2017
Provide additional exits
|