PRBD201706720
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Framing Inspection | Pending | |||
| Building Final Inspection | Pending | |||
| Fire Inspection Final | Pending | |||
| Framing Inspection | Failed | 9/7/2017 (10:00 - 12:00) | 9/7/2017 | 09/07/2017 |
| Need plumbing and electrical and HVAC permits, and rough in inspections. A) Need closet storage at bathroom cut open. B) Opening into new space may thru a building fire separation wall ? C) Existing building mechanical room - must be 1 hr rated, and separated from the new bathroom. Electrical panel is inside restroom, see electrical code. D) Need to see abondoned 1.5 inch horizontal pvc pipe, at doorway, as it may be a horizontal vent. | ||||
|
Corrections:
Miscellaneous/Other
Outstanding
09/08/2017
Framing - No one on site. A. Need plumbing, electrical, and HVAC permits. Need closet storage at restroom cut open prior to final. B. Opening into new expansion may be thru a building fire separation wall. C. Existing building mechanical room must be 1 hr rated, and separated from new tenant space. D. Electrical panel located in restroom, see electrical code for any requirements ? D. Need to see confirm 1.5 inch PVC pipe horizontally thru existing tenant expansion wall as it may be a horizontal plumbing vent pipe.
|
||||
| Framing Inspection | Partial Pass | 9/12/2017 (10:00 - 12:00) | 9/12/2017 | 09/12/2017 |
| Framing of walls only for new offices at this time. | ||||
|
Corrections:
Miscellaneous/Other
Outstanding
09/12/2017
A. Mechanical-electrical room requires 1 hour rated construction separation from new expanded tenant space. B. Walls and accessible counter are approved. C. Provide existing building plans to city to confirm location of fire walls for compartmentalizations of fire areas for the existing building .
|
||||