PRBD201707048
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Partial Pass | 9/11/2017 (12:30 - 2:30) | 9/11/2017 | 09/11/2017 |
Partial framing, see corrections. | ||||
Corrections:
Miscellaneous/Other
Outstanding
09/11/2017
Framing - A. Need front smoke wall ceiling framing to support storefront bulkhead completed. Need more firecaulking at new thru floor plastic 2 inch plumbing penetrations completed. Approved. B. Call for above ceiling for all trade inspections, fire sprinkler, HVAC, electrical, and plumbing rough in for New mop sink and\ store cabinet island vent and waste not installed] at this time.
|
||||
Framing Inspection | Passed w/ Conditions | 9/18/2017 (12:30 - 2:30) | 9/18/2017 | 09/18/2017 |
Corrections:
Miscellaneous/Other
Comment Only
09/18/2017
Approved to cover hard lids and drop panels in ceiling grids pending approval of sprinkler inspection.
|
||||
Framing Inspection | Passed | 10/13/2017 (10:00 - 12:00) | 10/13/2017 | 10/13/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/13/2017
Above ceiling approved pending sprinkler inspection.
|
||||
Fire Inspection Final | Passed w/ Conditions | 10/23/2017 (12:30 - 2:30) | 10/23/2017 | 10/23/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/23/2017
Fire Final Approved pending Building and Environmental Health Final Inspections
|
||||
Building Final Inspection | Failed | 10/23/2017 (12:30 - 2:30) | 10/23/2017 | 10/23/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/23/2017
1) space to be thoroughly cleaned. 2) install sprinkler escutcheon 3) corrections for E.H. To be completed. All items to be completed for final C.O.
Approved to stock and train. No final C.O. At this time.
|
||||
Building Final Inspection | Partial Pass | 10/27/2017 (8:00 - 10:00) | 10/27/2017 | 10/27/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/27/2017
Approved to open to public. 1) oven to have a type 2 hood , Hvac permit , electrical permit and inspections needed. No use of oven at this time. Approval given to open per E.H. And fire inspection.
|
||||
Building Final Inspection | Passed | 04/23/2018 | ||
Corrections:
Miscellaneous/Other
Comment Only
04/23/2018
The equipment that needed a hood was removed, there is nothing outstanding with this permit anymore. Final approved.
|