PRBD201710830
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Framing Inspection | Pending | |||
| Building Final Inspection | Pending | |||
|
Corrections:
Miscellaneous/Other
Outstanding
02/16/2018
Need final fire approval.
|
||||
| Building Final Inspection | Pending | |||
| Framing Inspection | Partial Pass | 1/10/2018 (8:00 - 10:00) | 1/10/2018 | 01/10/2018 |
|
Corrections:
Miscellaneous/Other
Outstanding
01/10/2018
Framing - walls ok. A. Above ceiling-patch fireproofing 20 inch a 8 inch area under one beam. B. Install one fire damper in thru duct to corridor. C. Review of exit signs - yes, but also need emergency lighting for space ? D. Staple top edge of exterior scrim foil with drywall. E. CALL FOR above ceiling for fireproof patching, corridor wall INSPECTION BOTH SIDES firecaulked, and possibly with fire damper. E. Call for subcontractor above ceiling for electrical, low voltage, fire sprinkler, AND BUILDING INSPECTOR.
|
||||
| Building Final Inspection | Failed | 2/16/2018 (10:00 - 12:00) | 2/16/2018 | 02/16/2018 |
|
Corrections:
Miscellaneous/Other
Carried Forward
02/16/2018
Need final fire approval.
|
||||
| Fire Inspection Final | Passed | 2/16/2018 (10:00 - 12:00) | 2/16/2018 | 03/01/2018 |
| Must test fire alarm devices. | ||||
| Fire Inspection Final | Passed | 03/01/2018 | ||
| Building Final Inspection | Failed | 2/22/2018 (10:00 - 12:00) | 2/22/2018 | 03/01/2018 |