PRBD201710919
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Passed | 1/12/2018 (8:00 - 10:00) | 1/12/2018 | 01/12/2018 |
Corrections:
Miscellaneous/Other
Comment Only
01/12/2018
Framing approved, no electrical going in the walls. Ok to cover.
Sprinkler work is contracted by owner, it doesn’t appear that any work is needed. If work is to be done the contractor will need to obtain permit and inspections.
|
||||
Fire Inspection Final | Passed w/ Conditions | 1/25/2018 (12:30 - 2:30) | 1/25/2018 | 01/26/2018 |
Corrections:
Fire extinguisher(s) needed.
Comment Only
01/26/2018
Fire extinguisher(s) needed. Hang new fire extinguishers in locations discussed prior to opening of store.
Contractor was in the process of removing hasp and installing panic hardware on rear exit door. COB Building Inspector to follow up on his final.
|
||||
Building Final Inspection | Partial Pass | 1/26/2018 (8:00 - 10:00) | 1/26/2018 | 01/26/2018 |
Corrections:
Miscellaneous/Other
Outstanding
01/26/2018
Install bench and accessibility signage to the fitting room. Recheck at final.
|
||||
Miscellaneous/Other
Comment Only
01/26/2018
Occupancy load includes reduction for fixtures and puts it under 50.
See accessibility requirements for the fitting room and install as required.
Approved to stock, any opening of store is at their own risk due to not having the fitting room completed.
|
||||
Building Final Inspection | Failed | 4/13/2018 (10:00 - 12:00) | 4/13/2018 | 04/13/2018 |
Corrections:
Miscellaneous/Other
Carried Forward
04/13/2018
Accessible bench in fitting room is too short in length per code requirements, and signage was removed.
Correct to make code compliant and call for inspection.
|
||||
Building Final Inspection | Passed | 09/21/2018 | ||
Corrections:
Miscellaneous/Other
Comment Only
09/21/2018
Accessible bench in fitting room is too short in length per code requirements, and signage was removed.
Correct to make code compliant and call for inspection.
|
||||
Miscellaneous/Other
Comment Only
09/21/2018
This store has closed down, the corrections were never made during the time it was open.
This permit is now expired and closed.
|