Permit Application Status

PRBD201710919


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRBD201710919
Building
Finaled
MOAC MALL HOLDINGS LLC
Alteration/Remodel
Mercantile
Miniml Tenant improvement of an existing 3016 square foot retail space, architectural only, MEP is design build under a separate submittal by the general contractor
11/13/2017
01/04/2018
03/20/2019

Locations

Permits

Permit Number: PRBD201710919

Building
Finaled
01/04/2018
03/20/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Passed 1/12/2018 (8:00 - 10:00) 1/12/2018 01/12/2018
Corrections:


Miscellaneous/Other
Comment Only
01/12/2018
Framing approved, no electrical going in the walls. Ok to cover. Sprinkler work is contracted by owner, it doesn’t appear that any work is needed. If work is to be done the contractor will need to obtain permit and inspections.

Fire Inspection Final Passed w/ Conditions 1/25/2018 (12:30 - 2:30) 1/25/2018 01/26/2018
Corrections:


Fire extinguisher(s) needed.
Comment Only
01/26/2018
Fire extinguisher(s) needed. Hang new fire extinguishers in locations discussed prior to opening of store. Contractor was in the process of removing hasp and installing panic hardware on rear exit door. COB Building Inspector to follow up on his final.

Building Final Inspection Partial Pass 1/26/2018 (8:00 - 10:00) 1/26/2018 01/26/2018
Corrections:


Miscellaneous/Other
Outstanding
01/26/2018
Install bench and accessibility signage to the fitting room. Recheck at final.

Miscellaneous/Other
Comment Only
01/26/2018
Occupancy load includes reduction for fixtures and puts it under 50. See accessibility requirements for the fitting room and install as required. Approved to stock, any opening of store is at their own risk due to not having the fitting room completed.

Building Final Inspection Failed 4/13/2018 (10:00 - 12:00) 4/13/2018 04/13/2018
Corrections:


Miscellaneous/Other
Carried Forward
04/13/2018
Accessible bench in fitting room is too short in length per code requirements, and signage was removed. Correct to make code compliant and call for inspection.

Building Final Inspection Passed 09/21/2018
Corrections:


Miscellaneous/Other
Comment Only
09/21/2018
Accessible bench in fitting room is too short in length per code requirements, and signage was removed. Correct to make code compliant and call for inspection.

Miscellaneous/Other
Comment Only
09/21/2018
This store has closed down, the corrections were never made during the time it was open. This permit is now expired and closed.