PRBD201711945
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Framing Inspection | Partial Pass | 1/24/2018 (8:00 - 10:00) | 1/24/2018 | 01/24/2018 |
|
Corrections:
Miscellaneous/Other
Outstanding
01/24/2018
Framing - walls for new tenant - approved. A. Existing fireproofing for tenant space - approved. B. One area of space is open ceiling to fireproofing of I beams, and balance of space is ceiling tile plenum ceiling. C. Call for above ceiling inspection for electrical, low voltage, plumbing if required, fire sprinkler (heads up and down), HVAC, and HVAC fire dampers w/ access, and fire caulking of 1 hour walls to steel deck both sides only along the new tenant elevator lobby corridor walls.
|
||||
| Fire Inspection Final | Passed | 3/2/2018 (12:30 - 2:30) | 3/2/2018 | 03/01/2018 |
| Building Final Inspection | Passed | 3/2/2018 (12:30 - 2:30) | 3/2/2018 | 03/02/2018 |