PRBD201802160
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Partial Pass | 4/4/2018 (12:30 - 2:30) | 4/4/2018 | 04/04/2018 |
Corrections:
Miscellaneous/Other
Outstanding
04/04/2018
1) change out standard track at far wall , and replace with deep track for deflection. Remove screws holding studs in place and when installing gypsum do not attach to deep track.
Send picture of deep track replacement to inspector.
|
||||
Miscellaneous/Other
Comment Only
04/04/2018
Approved to cover walls, with the pending outstanding comment to be corrected.
Inwall Piping to be cut off and capped and inspected.
The electrical boxes being removed at back of stair wall, patches to be properly staggered. Provide pictures to inspector.
|
||||
Fire Inspection Final | Passed | 05/09/2018 | ||
Building Final Inspection | Passed | 5/15/2018 (2:30 - 3:30) | 5/15/2018 | 05/15/2018 |
DO NOT SCHEDULE FINAL UNTIL SAC DETERMINATION IS RECEIVED. Beyer Kelly 04/10/2018 9:45 AM | ||||
Corrections:
Miscellaneous/Other
Comment Only
05/15/2018
Final approved, ok to occupy
|