PRBD201808283
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Building Final Inspection | Pending | |||
| Framing Inspection | Passed | 11/19/2018 (8:00 - 10:00) | 11/19/2018 (AM) | 11/19/2018 |
| 11/15/18 framing inspection cancelled by contractor. vcarlson 11/14/2018 9:05 AM | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
11/19/2018
Framing approved.
1) Fire stops to be viewed from below since 11 fire collars also to be viewed.
2) Wood at storefront have gypsum installed underneath, against framing.
|
||||
| Above Ceiling Inspection | Passed | 12/14/2018 (10:00 - 12:00) | 12/14/2018 (AM) | 12/14/2018 |
|
Corrections:
Miscellaneous/Other
Outstanding
12/14/2018
Piping in ceiling was cut and abandoned,( could not verify if metal or plastic) install appropriate firestop to pipe. Located 5 ft back into space above the kitchen equipment from the floor above. Same location... remove lose insulation or properly wrap the duct where insulation is torn away.
Recheck at next inspection.
|
||||
|
Miscellaneous/Other
Comment Only
12/14/2018
Above ceiling approved pending the correction of “outstanding “ being done. Will reinspect at next inspection.
|
||||
| Fire Inspection Final | Passed | 12/17/2018 (2:30 - 3:30) | 12/17/2018 (PM) | 12/17/2018 |
| Building Final Inspection | Failed | 12/17/2018 (2:30 - 3:30) | 12/17/2018 (PM) | 12/17/2018 |
|
Corrections:
Miscellaneous/Other
Comment Only
12/17/2018
Extensive corrections with E.H. And plumbing corrections. No temp at this time, correct items and call for inspection.
|
||||
| Building Final Inspection | Partial Pass | 12/18/2018 (2:30 - 3:30) | 12/18/2018 (PM) | 12/18/2018 |
|
Corrections:
Miscellaneous/Other
Comment Only
12/18/2018
Approval to open for business to public... final is pending approval by E.H. And a set completion date is for 1/7/19 for all E.H. Approval final.
|
||||