PRBD201808522
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Footing Inspection | Partial Pass | 9/6/2018 (12:30 - 2:30) | 9/6/2018 | 09/06/2018 |
Corrections:
Miscellaneous/Other
Comment Only
09/06/2018
Footings and rebar approved to place concrete.
|
||||
Footing Inspection | Failed | 9/27/2018 | 09/27/2018 | |
Corrections:
Miscellaneous/Other
Comment Only
09/27/2018
Rebar is not ready for inspection , call and set up inspection when ready.
|
||||
Footing Inspection | Passed | 10/4/2018 (8:00 - 10:00) | 10/4/2018 | 10/04/2018 |
Corrections:
Miscellaneous/Other
Comment Only
10/04/2018
Rebar installation is as per design. Approved to place concrete.
|
||||
Framing Inspection | Passed | 11/8/2018 (12:30 - 2:30) | 11/8/2018 (PM) | 11/08/2018 |
Corrections:
Miscellaneous/Other
Comment Only
11/08/2018
Above ceiling approved.
|
||||
Fire Inspection Final | Failed | 12/17/2018 (8:00 - 10:00) | 12/17/2018 (AM) | 12/17/2018 |
Corrections:
Miscellaneous/Other
Outstanding
12/17/2018
Fire Final Not Approved. Need to close out fire alarm and sprinkler permits prior to Fire Final for building permit.
|
||||
Building Final Inspection | Failed | 12/17/2018 (8:00 - 10:00) | 12/17/2018 (AM) | 12/17/2018 |
Corrections:
Miscellaneous/Other
Comment Only
12/17/2018
Open permits... Hvac 201813236,
Sprinkler 201812239, Electrical 201814174, Alarm 201814172. These permits need have inspections performed and to be closed out for final of the building permit. Call in for all inspections prior to obtaining building final.
|
||||
Fire Inspection Final | Passed | 1/22/2019 (8:00 - 10:00) | 1/22/2019 (AM) | 01/22/2019 |
Building Final Inspection | Passed | 1/22/2019 (8:00 - 10:00) | 1/22/2019 (AM) | 01/22/2019 |
Corrections:
Miscellaneous/Other
Outstanding
01/22/2019
Final approved pending mechanical permit final with balancing report needed and sent to Inspector.
|