PRBD201809558
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Partial Pass | 10/29/2018 (8:00 - 10:00) | 10/29/2018 (AM) | 10/29/2018 |
Framing- A NO WALL ROUGH IN SIGNATURES ON PERMIT CARD FOR TRADES- A. electrical, B. plumbing. C. WALL FRAMING - PARTIAL APPROVED ONLY. NO ONE FROM CRAWFORD MERTZ ON SITE. | ||||
Corrections:
Miscellaneous/Other
Carried Forward
10/29/2018
Framing request - A. Permit card has no electrical or plumbing rough in signatures on card. B. IF THESE WERE INSPECTED BY BLOOMINGTON...the permit card was not posted on site. This is THE PERMIT HOLDERS FAULT. DO NOT COVER, UNTIL CONFIRMING THE ABOVE.
|
||||
Framing Inspection | Passed | 11/6/2018 (12:30 - 2:30) | 11/6/2018 (PM) | 11/06/2018 |
Corrections:
Miscellaneous/Other
Outstanding
10/29/2018
Framing request - A. Permit card has no electrical or plumbing rough in signatures on card. B. IF THESE WERE INSPECTED BY BLOOMINGTON...the permit card was not posted on site. This is THE PERMIT HOLDERS FAULT. DO NOT COVER, UNTIL CONFIRMING THE ABOVE.
|
||||
Fire Inspection Final | Not Ready | 12/19/2018 (10:00 - 12:00) | 12/19/2018 (AM) | 12/19/2018 |
Nick called to cancel his inspection for final today with fire and bldg as plumbing was not ready; I called Kris and Brian. jsmidt 12/19/2018 10:36 AM | ||||
Building Final Inspection | Failed | 12/19/2018 (10:00 - 12:00) | 12/19/2018 (AM) | 12/19/2018 |
Accessible transfer showers - back wall and seat required. Fire sprinkler 10-12 - painted sprinkler heads, all to be replaced. Mag loc entry/exit door must open and drop off on fire alarm. Occupant load should be less than 50, or exit door hardware is wrong type. | ||||
Fire Inspection Final | Failed | 1/3/2019 (8:00 - 10:00) | 1/3/2019 (AM) | 01/03/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
01/03/2019
Fire alarm and access control must be tested.
|
||||
Building Final Inspection | Partial Pass | 1/3/2019 (8:00 - 10:00) | 1/3/2019 (AM) | 01/03/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
01/03/2019
Final for new fitness center- pending....A. Men’s & women’s transfer type accessible shower wall and seat, including all horizontal and vertical grab bars must be installed. B Two - existing 3 riser stairways serving the spinning room, as part of the whole new fitness center, requires handrails with 12 inch horizontal extensions and returned ends, where practically feasible, on both sides of stairways, at a height of 34-38 inches above the tread nosings of the two stairways. C. Final of all other trade inspections.
|
||||
Fire Inspection Final | Passed | 2/28/2019 (10:00 - 12:00) | 2/28/2019 (AM) | 02/28/2019 |
Corrections:
Miscellaneous/Other
Outstanding
01/03/2019
Fire alarm and access control must be tested.
|
||||
Building Final Inspection | Passed | 2/28/2019 (10:00 - 12:00) | 2/28/2019 (AM) | 02/28/2019 |
Corrections:
Miscellaneous/Other
Outstanding
01/03/2019
Final for new fitness center- pending....A. Men’s & women’s transfer type accessible shower wall and seat, including all horizontal and vertical grab bars must be installed. B Two - existing 3 riser stairways serving the spinning room, as part of the whole new fitness center, requires handrails with 12 inch horizontal extensions and returned ends, where practically feasible, on both sides of stairways, at a height of 34-38 inches above the tread nosings of the two stairways. C. Final of all other trade inspections.
|