PRBD201812540
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Partial Pass | 3/1/2019 (10:00 - 12:00) | 3/1/2019 (AM) | 03/01/2019 |
Corrections:
Miscellaneous/Other
Comment Only
03/01/2019
Walls approved to cover.
Ceilings and storefront to be left open for inspections, no covering.
|
||||
Framing Inspection | Passed | 3/12/2019 (8:00 - 10:00) | 3/12/2019 (AM) | 03/12/2019 |
Corrections:
Miscellaneous/Other
Comment Only
03/12/2019
Storefront and hard lids approved.
Remove the wood planking in ceiling of storefront that is used by electrical as a temp standing platform when doing work. Electrical inspection needed prior to covering at storefront.
|
||||
Progress Inspection | Partial Pass | 04/10/2019 | ||
Corrections:
Miscellaneous/Other
Comment Only
04/10/2019
1) maintain clearances in accessible fitting room as per code requirements.
2) install directional exit in back storage room at office wall. Remove exit sign over fitting room inside entry.
3) contractor to check EM lighting in back store area and install as needed to provide as required.
|
||||
Fire Inspection Final | Partial Pass | 4/11/2019 (12:30 - 2:30) | 4/11/2019 (PM) | 04/11/2019 |
Corrections:
Miscellaneous/Other
Comment Only
04/11/2019
Ok to stock.
|
||||
Building Final Inspection | Partial Pass | 4/11/2019 (12:30 - 2:30) | 4/11/2019 (PM) | 04/11/2019 |
Corrections:
Miscellaneous/Other
Comment Only
04/11/2019
Exit signage corrected and fitting room corrected. EM lighting checked and compliant.
1) fix or replace the one broken EM light in storage and exit frog eyes to be on EM lighting.
Electrical has issues with UL listing, these issues to be completed prior to the full final.
Approved for stock and setup of space.
|
||||
Fire Inspection Final | Passed | 4/18/2019 (10:00 - 12:00) | 4/18/2019 (AM) | 04/18/2019 |
Building Final Inspection | Passed | 4/18/2019 (10:00 - 12:00) | 4/18/2019 (AM) | 04/18/2019 |
Corrections:
Miscellaneous/Other
Comment Only
04/18/2019
Final approved for occupancy and public use.
Electrical has approved final based that all the covers to the signs are installed.
|