Summary

PRBD201812540
Building
Finaled
MOAC MALL HOLDINGS LLC
Alteration/Repair/Replace
Not Required
Remodel of the existing Finishline store into a JD Sports store.
10/12/2018
02/06/2019
10/15/2019
04/18/2019

Locations

Permits

Permit Number: PRBD201812540

Building
Finaled
02/06/2019
10/15/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Partial Pass 3/1/2019 (10:00 - 12:00) 3/1/2019 (AM) 03/01/2019
Corrections:


Miscellaneous/Other
Comment Only
03/01/2019
Walls approved to cover. Ceilings and storefront to be left open for inspections, no covering.

Framing Inspection Passed 3/12/2019 (8:00 - 10:00) 3/12/2019 (AM) 03/12/2019
Corrections:


Miscellaneous/Other
Comment Only
03/12/2019
Storefront and hard lids approved. Remove the wood planking in ceiling of storefront that is used by electrical as a temp standing platform when doing work. Electrical inspection needed prior to covering at storefront.

Progress Inspection Partial Pass 04/10/2019
Corrections:


Miscellaneous/Other
Comment Only
04/10/2019
1) maintain clearances in accessible fitting room as per code requirements. 2) install directional exit in back storage room at office wall. Remove exit sign over fitting room inside entry. 3) contractor to check EM lighting in back store area and install as needed to provide as required.

Fire Inspection Final Partial Pass 4/11/2019 (12:30 - 2:30) 4/11/2019 (PM) 04/11/2019
Corrections:


Miscellaneous/Other
Comment Only
04/11/2019
Ok to stock.

Building Final Inspection Partial Pass 4/11/2019 (12:30 - 2:30) 4/11/2019 (PM) 04/11/2019
Corrections:


Miscellaneous/Other
Comment Only
04/11/2019
Exit signage corrected and fitting room corrected. EM lighting checked and compliant. 1) fix or replace the one broken EM light in storage and exit frog eyes to be on EM lighting. Electrical has issues with UL listing, these issues to be completed prior to the full final. Approved for stock and setup of space.

Fire Inspection Final Passed 4/18/2019 (10:00 - 12:00) 4/18/2019 (AM) 04/18/2019
Building Final Inspection Passed 4/18/2019 (10:00 - 12:00) 4/18/2019 (AM) 04/18/2019
Corrections:


Miscellaneous/Other
Comment Only
04/18/2019
Final approved for occupancy and public use. Electrical has approved final based that all the covers to the signs are installed.