PRBD201813732
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Above Ceiling Inspection | Passed | 10/24/2019 | ||
Corrections:
Miscellaneous/Other
Comment Only
10/24/2019
Inspections were done with the inspections for the store renovation... see the permit inspection notes for inspections.
|
||||
Framing Inspection | Passed | 10/24/2019 | ||
Corrections:
Miscellaneous/Other
Comment Only
10/24/2019
See the inspections for the renovation of Nordstroms for any inspections to this restaurant.
All framing and firestops approved.
|
||||
Building Final Inspection | Failed | 10/17/2019 (12:30 - 2:30) | 10/24/2019 (PM) | 10/24/2019 |
Corrections:
Miscellaneous/Other
Comment Only
10/24/2019
1) corrections for Environmental Health to be completed.
2) install occupancy load signage.
3) seating for accessibility to comply with the calculated load count, 9 seats to be designated for accessibility per the approved plans.
4) fire alarm and sprinkler final to be completed with inspection
5) corrections at hood and Ansil system per fire inspection to be completed.
Final for this permit is not ready.
|
||||
Fire Inspection Final | Passed | 10/24/2019 (12:30 - 2:30) | 10/24/2019 (PM) | 10/25/2019 |
Building Final Inspection | Passed | 10/25/2019 (2:30 - 3:30) | 10/25/2019 (PM) | 10/25/2019 |
Corrections:
Miscellaneous/Other
Comment Only
10/25/2019
Temp signage is in place until the permanent signs are made up and installed.
All inspections with this remodel are completed.
Ok to obtain liquor license, and ok to open to public.... Final approved.
|