PRBD201901852
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Framing Inspection | Partial Pass | 4/1/2019 (2:30 - 3:30) | 4/1/2019 (PM) | 04/01/2019 |
| progress inspection. | ||||
| Framing Inspection | Partial Pass | 4/1/2019 (2:30 - 3:30) | 4/1/2019 (PM) | 04/01/2019 |
| floor 21. Build out of existing north west vacancy for existing tenant Total Dynamics. A. Patch fireproofing on existing steel beams. B. Scrim foil protection above windows to concrete floor above. C. Rated 1 hr corridor requiring smoke fire dampers and 1 hour walls to deck above. D. Remove ceiling tiles to view existing above ceiling conditions, and call for reinspection. | ||||
| Progress Inspection | Passed | 4/12/2019 (8:00 - 10:00) | 4/12/2019 (AM) | 04/12/2019 |
| Need fire sprinkler and horn strobe above ceiling WORK AND inspection, by LSS COMPANY. A. Verbal order to install 90 minute wall packs through out, for loss of power EM lighting BY Extreme Electric. B. Patch fireproofing , and exterior rim scrim foil protection- approved. C. Need HVAC permit for all above ceiling new work if applicable. D. Design has ceiling tile, for complete plenum return air, from building floor main return air duct opening, approved. | ||||
| Building Final Inspection | Issue TCO | 5/9/2019 (10:00 - 12:00) | 5/9/2019 (AM) | 05/09/2019 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/09/2019
BUILDING Temp C O - APPROVED. A. ALL TRADE INSPECTIONS HAVE ISSUED TEMP C O . OFFICE FURNITURE IS BACKORDERED,.
|
||||
| Building Final Inspection | Passed | 7/11/2019 (2:30 - 3:30) | 7/11/2019 (PM) | 07/11/2019 |
|
Corrections:
Miscellaneous/Other
Outstanding
07/11/2019
Final - approved. Outstanding issues. A. Provide smoke gaskets to the two metal doors exiting into the rated corridor. B. Complete ceiling tiles for furniture feeds running thru ceiling tiles into the plenum ceiling above.
|
||||
| Fire Inspection Final | Passed | 7/11/2019 (2:30 - 3:30) | 7/11/2019 (PM) | 07/31/2019 |
| Fire Inspection Final | Passed | 7/31/2019 (12:30 - 2:30) | 7/31/2019 (PM) | 07/31/2019 |