Permit Application Status

PRBD201903535


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRBD201903535
Building
Expired
CITY OF BLOOMINGTON
Alteration/Repair/Replace
Not Required
Remodel of existing locker rooms, adding ADA ramps, remodel/addition of front vestibule at Bloomington Ice Garden
04/17/2019
06/12/2019
01/23/2021

Locations

Permits

Permit Number: PRBD201903535

Building
Expired
06/12/2019
01/23/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Walk-through Inspection Passed 5/2/2019 05/02/2019
On site meeting with the contractor, Robert Howell, Deb Williams, Pete Miller and myself to discuss exiting/temporary structural components for occupants during the different phases of the construction project.
Footing Inspection Partial Pass 7/11/2019 (12:30 - 2:30) 7/11/2019 (PM) 07/11/2019
Poured west end new vestibule footings. Note 24 inch round RCP storm/sewer pipe exposed at bottom of footing elevation, running from east to west thru new footing. Pour isolated today, each side of pipe today, for engineering analysis or fix or coverage.
Footing Inspection Partial Pass 7/25/2019 (10:00 - 12:00) 7/25/2019 (AM) 07/25/2019
Ongoing - pouring a specific reinforced center section of stoop footing under the existing building RCP concrete pipe discovered during excavation, per engineers revision design.
Progress Inspection Partial Pass 08/05/2019
Progress - A. REVIEW SITE PLAN APPROVED BY JULIE LONG, CITY ENGINEERING. NO BUILDING INSPECTION APPROVAL FOR SITE PLAN REVISION 05/28/2019. B. MN ACCESSIBILITY CODE - FOR WEST NEW MAIN ENTRANCE WITH RAMPS AND MAX SLOPES, CLOSEST ACCESSIBILITY PARKING AREA, UNLOADING,
Complaint Inspection Failed 08/06/2019
BUILDING Plan review - HAS NOT BEEN PERFORMED BY BUILDING INSPECTION. A. ACCESSIBILITY PLAN is not compliant with new MN state 2015 accessibility and IBC Codes, regarding steps, handrails, ramps, ramp rails, curb cuts, transfer showers, roll in showers, accessibility parking, and parking location, and parking signage. B. Note-this is an existing building. C. Architect has not used MN STATE 2015 ACCESSIBILITY CODE, AND USED A FEDERAL ANSI CODE NOT ALLOWED IN THE STATE OF MN. (See City plan issued )
Framing Inspection Partial Pass 8/9/2019 (10:00 - 12:00) 8/9/2019 (AM) 08/09/2019
Small infill and soffit steel stud framing in locker room areas at ceiling area. No rating. OK TO COMPLETE .
Framing Inspection Partial Pass 8/27/2019 (8:00 - 10:00) 8/27/2019 (AM) 08/27/2019
Framing - LOCATION WEST NEW ENTRY VESTIBULE. A. Steel stud framing, parapet, infill, wall. B. Pinnacle company, framing contractors. C. Rain liter roof drain piping by Kieth Pumper plumbing. D. Ok to proceed, and insulate exterior walls min R20, architect wants mineral wool fiber insulation. Cavity should be full to prevent settlement.
Progress Inspection Partial Pass 10/8/2019 (12:30 - 2:30) 10/8/2019 (PM) 10/08/2019
Need more time for next progress inspection.
Fire Inspection Final Partial Pass 10/21/2019 (8:00 - 10:00) 10/21/2019 (AM) 10/21/2019
Corrections:


Miscellaneous/Other
Comment Only
10/21/2019
Ok to occupy locker rooms. 30 day temp CO. Building must still check off.

Building Final Inspection Partial Pass 10/21/2019 (8:00 - 10:00) 10/21/2019 (AM) 10/21/2019
Progress - A. LOCKER ROOMS, RESTROOMS EAST SIDE. Finish grab bars, seats, toilet paper dispensers. B. Fire and electrical have approved these areas for safety. C. Building temp occupancy for locker rooms requires completing locker room fixtures, benches, signage, drinking fountain, etc.
Fire Inspection Final Failed 1/13/2020 (8:00 - 10:00) 1/13/2020 (AM) 01/13/2020
3 painted sprinkler heads in rink 1 locker room A, 1 painted sprinkler head in rink 1 locker room C.
Building Final Inspection Partial Pass 1/13/2020 (8:00 - 10:00) 1/13/2020 (AM) 01/13/2020
Final requires - A. Exterior existing accessible parking stalls and unload stalls - location north west parking lot. B. If new accessible parking lot stripping, have a minimum 96 inch wide parking stall width, and 96 inch unload stalls with signage per MN state accessible code. Location of accessible parking to be near north west side of new building accessible sidewalk for new main entrance addition. Per MN state 2015 accessibility code - 8 accessible parking stalls for 400 total parking spaces, or 6 for 200 parking spaces. B. Accessible entrance/exit doors are not required to have a new accessible push button to open new entry doors. C. Accessible Signage on new and existing locker rooms have been installed. D. Concessions - see environmental health permit ? Possibly no work per the city of Bloomington. E. Final - Fire, HVAC, Electrical, and mechanical permits, are required prior to building final. F. Existing building - pre existing South west accessible parking signage.
Fire Inspection Final Passed 1/27/2020 (12:30 - 2:30) 1/27/2020 (PM) 02/13/2020
Building Final Inspection Passed 7/27/2020 07/27/2020