Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Partial Pass | 6/13/2019 (8:00 - 10:00) | 6/13/2019 (AM) | 06/13/2019 |
Corrections:
Miscellaneous/Other
Comment Only
06/13/2019
Back of house walls approved to cover.
Firestop needed at drain piping in bathroom.
|
||||
Framing Inspection | Partial Pass | 6/28/2019 (8:00 - 10:00) | 6/28/2019 (AM) | 06/28/2019 |
Corrections:
Miscellaneous/Other
Comment Only
06/28/2019
Walls of sales area and storefront walls only approved.
|
||||
Above Ceiling Inspection | Partial Pass | 7/11/2019 (12:30 - 2:30) | 7/11/2019 (PM) | 07/11/2019 |
Corrections:
Miscellaneous/Other
Comment Only
07/11/2019
Viewed sales are above ceiling... install access panel as marked in location on floor in back corner.
Pending sprinkler and mechanical approval for the sales area.. ok to cover.
|
||||
Above Ceiling Inspection | Passed | 8/15/2019 (8:00 - 10:00) | 8/15/2019 (AM) | 08/15/2019 |
Corrections:
Miscellaneous/Other
Comment Only
08/15/2019
Above ceiling in back of house at ACT tiled ceilings approved.
|
||||
Fire Inspection Final | Failed | 9/17/2019 (12:30 - 2:30) | 9/17/2019 (PM) | 09/17/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
09/18/2019
Exit doors shall comply with MN State Fire Code Section 1008.1. Which states the following:
"Means of egress doors shall be readily distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Mirrors or similar reflecting materials shall not be used on means of egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials"
Black, wood grain exit door on black wood grain wall shall, at a minimum, have a lighted exit sign above, stainless (or similar) steel kick and push plates, and contrasting color door frame.
The above item shall be completed prior to occupancy
|
||||
Building Final Inspection | Issue TCO | 9/17/2019 (12:30 - 2:30) | 9/17/2019 (PM) | 09/17/2019 |
9/17/2019 temp occupancy. 30 days A. Need final HVAC. B. MAIN EXIT DOOR MUST BE CONTRASTING TRIM AND CONTRASTING TOE KICK AND PUSH PLATE, PER FIRE MARSHAL. C.MN STATE ACCESSIBILITY - DRESSING ROOM. 1. DOOR STOP MOVED OFF FLOOR FOR 60 INCH TURNING RADIUS, AND COAT-HOOKS, MAX HEIGHT 48 INCHES ABOVE FINISHED FLOOR. D. Main transaction granite countertop 36 1/2 inch AFF, has additional pull out ON WALL NEXT TO TRANSACTION GRANITE COUNTERTOP. | ||||
Fire Inspection Final | Passed | 09/18/2019 | ||
Corrections:
Miscellaneous/Other
Resolved
09/18/2019
Exit doors shall comply with MN State Fire Code Section 1008.1. Which states the following:
"Means of egress doors shall be readily distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Mirrors or similar reflecting materials shall not be used on means of egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials"
Black, wood grain exit door on black wood grain wall shall, at a minimum, have a lighted exit sign above, stainless (or similar) steel kick and push plates, and contrasting color door frame.
The above item shall be completed prior to occupancy
|
||||
Building Final Inspection | Passed | 12/04/2019 | ||
Corrections:
Miscellaneous/Other
Comment Only
12/04/2019
Final approved
|