Summary

PRBD201905940
Building
Finaled
MOAC MALL HOLDINGS LLC
Alteration/Repair/Replace
Not Required
TENANT REMODEL INCLUDING MECHANICAL, ELECTRICAL, PLUMBING & NEW STOREFRONT.
06/06/2019
07/25/2019
05/17/2020
11/19/2019

Locations

Permits

Permit Number: PRBD201905940

Building
Finaled
07/25/2019
05/17/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Partial Pass 8/19/2019 (12:30 - 2:30) 8/19/2019 (PM) 08/19/2019
Corrections:


Miscellaneous/Other
Comment Only
08/19/2019
Viewed the back of house area of this store... framing that connects to ducting in any fashion to be disconnected and resupported as needed. Wall framing in this area approved and can be covered pending any electrical and plumbing inspections. Will view this area at next inspection for the disconnection of walls and ceilings from ducting support.

Framing Inspection Partial Pass 9/3/2019 (8:00 - 10:00) 9/3/2019 (AM) 09/03/2019
Corrections:


Miscellaneous/Other
Comment Only
09/03/2019
Walls at column line B to line F just south of line 2 which is back of sales area. Approved.

Miscellaneous/Other
Carried Forward
09/03/2019
Need information on the Celbar RX acoustic insulation. No spraying this product till it is reviewed for compliance.

Above Ceiling Inspection Partial Pass 9/12/2019 (8:00 - 10:00) 9/12/2019 (AM) 09/12/2019
See corrections. 6 framed and rocked “hard lid” back house rooms. Above ceiling - approved with conditions. SEE CORRECTIONS.
Corrections:


Miscellaneous/Other
Comment Only
09/12/2019
Above ceiling partial: 6 back house rooms having hard lid. 6 rooms marked on 11x17 city approved plan on site. A. Fireproofing - approved. B. Note- fire sprinkler, electrical, HVAC,and low voltage wiring must be inspected and approved prior to covering.(low voltage pending).

Above Ceiling Inspection Partial Pass 9/16/2019 (12:30 - 2:30) 9/16/2019 (PM) 09/16/2019
Above ceiling inspection locker rooms signed off on a plan for appropriate rooms.
Above Ceiling Inspection Partial Pass 9/18/2019 (12:30 - 2:30) 9/18/2019 (PM) 09/18/2019
Corrections:


Miscellaneous/Other
Comment Only
09/18/2019
Ceiling in men’s area approved. Ceiling in back Corredor approved.

Above Ceiling Inspection Partial Pass 9/25/2019 (8:00 - 10:00) 9/25/2019 (AM) 09/25/2019
Corrections:


Miscellaneous/Other
Comment Only
09/25/2019
Ceilings in woman’s fit and men’s sales.

Framing Inspection Passed 9/25/2019 (8:00 - 10:00) 9/25/2019 (AM) 09/25/2019
Corrections:


Miscellaneous/Other
Resolved
09/25/2019
Need information on the Celbar RX acoustic insulation. No spraying this product till it is reviewed for compliance.

Miscellaneous/Other
Comment Only
09/25/2019
Soffits, and partial storefront... approved

Above Ceiling Inspection Partial Pass 10/1/2019 (8:00 - 10:00) 10/1/2019 (AM) 10/01/2019
Corrections:


Miscellaneous/Other
Comment Only
10/01/2019
Soffits and storefront ceiling approved. Sprinkler inspection needed at storefront prior to covering. Disconnected duct in storefront ceiling to be reconnected prior to covering. The vestibule at the rear entry at the house is currently rated for one hour, I need to be ready for two hours. Contractor to verify with designer about moving the door to the two hour rated wall vs. relayering the 2 walls in he vestibule to maintain the 2 hour rating.

Above Ceiling Inspection Partial Pass 10/10/2019 (8:00 - 10:00) 10/10/2019 (AM) 10/10/2019
Corrections:


Miscellaneous/Other
Comment Only
10/10/2019
Above ceiling and framing of grow room, fuel bar soffit, and remainder of storefront soffit... approved

Building Final Inspection Failed 11/5/2019 (10:00 - 12:00) 11/5/2019 (AM) 11/05/2019
Corrections:


Miscellaneous/Other
Comment Only
11/05/2019
Not ready for final

Progress Inspection Partial Pass 11/05/2019
Corrections:


Miscellaneous/Other
Comment Only
11/05/2019
Above ceiling in the rooms with drop grids... approved

Fire Inspection Final Not Ready 11/5/2019 (AM) 11/07/2019
Progress Inspection Partial Pass 11/07/2019
Corrections:


Miscellaneous/Other
Comment Only
11/07/2019
Approved to bring in product for stock and setup.

Progress Inspection Partial Pass 11/07/2019
Corrections:


Miscellaneous/Other
Comment Only
11/07/2019
Approved to bring in product for stock and setup.

Building Final Inspection Not Ready 11/7/2019 (12:30 - 2:30) 11/7/2019 (PM) 11/07/2019
Corrections:


Miscellaneous/Other
Comment Only
11/07/2019
Not ready for final at this time. Approval given to bring in product and setup.

Building Final Inspection Not Ready 11/18/2019 (10:00 - 12:00) 11/18/2019 (AM) 11/18/2019
Corrections:


Miscellaneous/Other
Carried Forward
11/18/2019
1) Adjust the occupancy load signs that are installed to reflect the actual occupancy load as is on the approved plans in the sweat room, grow room and at the eating area. 2) Environmental Health approval needed, schedule inspection. 3) fire sign off for building permit and alarm permit needed, schedule inspection. 4) plumbing permit still open, back flow prevention needed at dispenser units. Correct and schedule plumbing inspection. 5) Hvac permit still open, permit to be final. Reschedule building final to coincide with all finals.

Fire Inspection Final Passed 11/19/2019 (10:00 - 12:00) 11/19/2019 (AM) 11/19/2019
Building Final Inspection Passed 11/19/2019 (10:00 - 12:00) 11/19/2019 (AM) 11/19/2019
Corrections:


Miscellaneous/Other
Comment Only
11/19/2019
Final approved, with verbal corrections to electrical contractor to add add directional arrows to certain signs of exit. This is happening as inspection is in progress. Environmental Health to follow up with there permit requirements once open for business.

Building Final Inspection VOID 11/19/2019
Corrections:


Miscellaneous/Other
Outstanding
11/18/2019
1) Adjust the occupancy load signs that are installed to reflect the actual occupancy load as is on the approved plans in the sweat room, grow room and at the eating area. 2) Environmental Health approval needed, schedule inspection. 3) fire sign off for building permit and alarm permit needed, schedule inspection. 4) plumbing permit still open, back flow prevention needed at dispenser units. Correct and schedule plumbing inspection. 5) Hvac permit still open, permit to be final. Reschedule building final to coincide with all finals.