PRBD201913198
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Passed w/ Conditions | 12/2/2019 (8:00 - 10:00) | 12/2/2019 (AM) | 12/02/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/02/2019
Metal wall framing approved pending electrical inspection,.. no covering electrical until inspected.
The wood built wall sections will need approximately 50 gallons of product coverage.
Leave empty pails onsite for inspection to verify product coverage.
|
||||
Fire Inspection Final | Failed | 12/18/2019 (10:00 - 12:00) | 12/18/2019 (AM) | 12/18/2019 |
Corrections:
Inadequate fire alarm coverage.
Outstanding
12/18/2019
kkaiser 12/18/2019 7:04 AM
Inadequate fire alarm coverage. Need to add fire alarm notification appliances.
|
||||
Building Final Inspection | Failed | 12/18/2019 (10:00 - 12:00) | 12/18/2019 | |
Cancelled per contractor. dheile 12/18/2019 9:34 AM | ||||
Corrections:
Miscellaneous/Other
Carried Forward
12/18/2019
Fire notification devices needed obtain permits and inspection.
Occupancy signage and the load count needed, which also triggers number of exits and the exiting paths through the space. Exit doors will also need to be marked and hardware at doors can be push to open with no latching inside of gaming area.
|
||||
Fire Inspection Final | Failed | 12/23/2019 (2:30 - 3:30) | 12/23/2019 (PM) | 12/23/2019 |
Corrections:
Miscellaneous/Other
Outstanding
12/23/2019
Several painted sprinkler heads found throughout space. Have sprinkler contractor inspect and replace painted heads as needed.
Sign and hang fire extinguishers as discussed.
Hang occupancy load signs for each gaming area as wells as main occupancy sign near entrance.
Need to retest emergency lights. Found a few that didn’t operate.
|
||||
Fire Inspection Final | Failed | 12/23/2019 | ||
Corrections:
Miscellaneous/Other
Carried Forward
12/23/2019
Several painted sprinkler heads found throughout space. Have sprinkler contractor inspect and replace painted heads as needed.
Sign and hang fire extinguishers as discussed.
Hang occupancy load signs for each gaming area as wells as main occupancy sign near entrance.
Need to retest emergency lights. Found a few that didn’t operate.
|
||||
Miscellaneous/Other
Carried Forward
12/23/2019
Several painted sprinkler heads found throughout space. Have sprinkler contractor inspect and replace painted heads as needed.
Sign and hang fire extinguishers as discussed.
Hang occupancy load signs for each gaming area as wells as main occupancy sign near entrance.
Need to retest emergency lights. Found a few that didn’t operate.
|
||||
Building Final Inspection | Passed | 12/26/2019 (2:30 - 3:30) | 12/26/2019 (PM) | 12/26/2019 |
Inspection canceled by contractor.NelsonThorpe Sarah 12/23/2019 12:24 PM | ||||
Corrections:
Miscellaneous/Other
Resolved
12/26/2019
Fire notification devices needed obtain permits and inspection.
Occupancy signage and the load count needed, which also triggers number of exits and the exiting paths through the space. Exit doors will also need to be marked and hardware at doors can be push to open with no latching inside of gaming area.
|
||||
Miscellaneous/Other
Comment Only
12/26/2019
All work and requirements are completed, approved for final and opening to public.
|
||||
Fire Inspection Final | Passed | 12/26/2019 (2:30 - 3:30) | 12/26/2019 (PM) | 12/26/2019 |
Corrections:
Miscellaneous/Other
Outstanding
12/23/2019
Several painted sprinkler heads found throughout space. Have sprinkler contractor inspect and replace painted heads as needed.
Sign and hang fire extinguishers as discussed.
Hang occupancy load signs for each gaming area as wells as main occupancy sign near entrance.
Need to retest emergency lights. Found a few that didn’t operate.
|
||||
Miscellaneous/Other
Resolved
12/26/2019
Several painted sprinkler heads found throughout space. Have sprinkler contractor inspect and replace painted heads as needed.
Sign and hang fire extinguishers as discussed.
Hang occupancy load signs for each gaming area as wells as main occupancy sign near entrance.
Need to retest emergency lights. Found a few that didn’t operate.
|