Summary

PRBD201914732
Building
Finaled
MSP SOUTHPOINT EQUITIES LLC
Alteration/Repair/Replace
Not Required
office remodel
12/09/2019
01/17/2020
11/15/2020
05/19/2020

Locations

Permits

Permit Number: PRBD201914732

Building
Finaled
01/17/2020
11/15/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Passed 1/29/2020 (10:00 - 12:00) 1/29/2020 (AM) 01/29/2020
Framing - pass. A. Call for above ceiling inspections for all trade inspections - fire sprinkler, electrical, and low voltage, mechanical, and plumbing final for existing break room - having new fixtures. B. (Break room Accessibility) must meet MN STATE 2015 accessibility code.
Progress Inspection Partial Pass 2/26/2020 (8:00 - 10:00) 2/26/2020 (AM) 02/26/2020
Above ceiling. - A. NEED ABOVE CEILING FOR NEW FIRE SPRINKLER AND ELECTRICAL / LOW VOLTAGE/FIRE ALARM WIRE. PLENUM AND OPEN CEILING RATED WIRE. PARTIAL PASS ONLY. Above grid inspection. dheile 02/24/2020 10:34 AM
Fire Inspection Final VOID 4/22/2020 (10:00 - 12:00) 4/22/2020 (AM) 04/14/2020
Building Final Inspection Failed 4/28/2020 (8:00 - 10:00) 4/28/2020 (AM) 04/28/2020
Gardner Builders. A. Need fire marshal final reinspection scheduled for two corrections today. 1. Need mag lock tested on fire alarm to release, and need a painted sprinkler head replaced. 2. Need to reschedule final fire marshal and final building re inspection together same day.
Fire Inspection Final Partial Pass 4/28/2020 (8:00 - 10:00) 4/28/2020 (AM) 04/28/2020
Fire Inspection Final Not Ready 5/6/2020 (7:00 - 8:00) 5/6/2020 (AM) 05/06/2020
Building Final Inspection Failed 5/6/2020 (8:00 - 10:00) 5/6/2020 (AM) 05/06/2020
Need fire final. Fire final today did not pass. Mag lock on space must release upon fire alarm.
Fire Inspection Final Passed 5/19/2020 (7:00 - 8:00) 5/19/2020 (AM) 05/19/2020
Building Final Inspection Passed 5/19/2020 (12:30 - 2:30) 5/19/2020 (PM) 05/19/2020
All trade inspections are final approved.