Permit Application Status

PRBD202000075


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRBD202000075
Building
Finaled
MSP SOUTHPOINT EQUITIES LLC
Alteration/Repair/Replace
Not Required
Corporate Office Remodel at Southpoint West Office Building in Bloomington, MN. Existing tenant of suite 175 is expanding into the give-back space of neighboring tenant.
01/03/2020
02/13/2020
11/09/2020
05/13/2020

Locations

Permits

Permit Number: PRBD202000075

Building
Finaled
02/13/2020
11/09/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Partial Pass 3/9/2020 (10:00 - 12:00) 3/9/2020 (AM) 03/09/2020
Rescheduled as electrical not able to be scheduled. jsmidt 03/05/2020 8:39 AM
Corrections:


Miscellaneous/Other
Comment Only
03/09/2020
Footings for area well on S.W. end ... approved

Framing Inspection Partial Pass 03/09/2020
Corrections:


Miscellaneous/Other
Comment Only
03/09/2020
Wall framing and soffit framing... contractor did not take into account deflection at walls that connect to the soffits, they take on the responsibility of any issues that may arise due to this framing method used. Approved to cover

Miscellaneous/Other
Outstanding
03/09/2020
Firestop at the low voltage wiring that penetrates through the floor inside the chase will have to be installed and viewed from the parking area below. The narrow soffit at the front of space is supported off the duct supports and is to be resupported independent of soffit... this needs to be checked at next inspection , lift ceiling tiles for inspector to verify.

Framing Inspection Passed 4/21/2020 (2:30 - 3:30) 4/21/2020 (PM) 04/21/2020
Phase 2 of 2. A. Framing-passed. B. Need all trade rough in inspections passed, for walls and above ceiling , prior to covering. B. Upon final inspection, must inspect floor penetrations from parking ramp below, for fire caulk, for electrical non rated floor box, and low voltage chase. Contractor on site today. Permit Card on site today.
Building Final Inspection Passed 5/13/2020 (8:00 - 10:00) 5/13/2020 (AM) 05/13/2020
Fire Inspection Final Passed 5/13/2020 (8:00 - 10:00) 5/13/2020 (AM) 05/13/2020