Permit Application Status

PRBD202001372


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRBD202001372
Building
Expired
POLAR SEMICONDUCTOR INC
Alteration/Repair/Replace
Not Required
P1 Storage Modification
02/13/2020
03/13/2020
01/30/2021

Locations

Permits

Permit Number: PRBD202001372

Building
Expired
03/13/2020
01/30/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Inspection Final Pending 8/3/2020 (8:00 - 10:00)
Framing Inspection Passed 4/6/2020 (12:30 - 2:30) 4/6/2020 (PM) 04/06/2020
Corrections:


Miscellaneous/Other
Comment Only
04/06/2020
Wafer pack room and gown room wall framing ... approved

Building Final Inspection Failed 6/26/2020 (8:00 - 10:00) 6/26/2020 (AM) 06/26/2020
Corrections:


Miscellaneous/Other
Carried Forward
06/26/2020
Chemical storage room , no framing inspection for building of shaft. 1) Piping being run through the cored holes needs to be firestopped. 2) provide special inspection report for the newly built block walls.

Fire Inspection Final Not Ready 6/26/2020 (8:00 - 10:00) 6/26/2020 (AM) 06/29/2020
Progress Inspection Passed 06/30/2020
Corrections:


Miscellaneous/Other
Comment Only
06/30/2020
CMU walls are laid in stack bond, with horizontal reinforcing installed at 16” o.c. Horizontal bond beam with 2 #5 rebar installed at top of wall.

Building Final Inspection Passed w/ Conditions 8/3/2020 (8:00 - 10:00) 8/3/2020 (AM) 08/03/2020
Corrections:


Miscellaneous/Other
Resolved
08/03/2020
Chemical storage room , no framing inspection for building of shaft. 1) Piping being run through the cored holes needs to be firestopped. 2) provide special inspection report for the newly built block walls.

Miscellaneous/Other
Comment Only
08/03/2020
Final approved for this room, sprinkler inspection and final is needed and to be completed.