Summary

PRBD202003450
Building
Finaled
G&I VIII WF PLAZA LLC
Alteration/Repair/Replace
Not Required
Interior tenant build-out
04/14/2020
04/30/2020
05/09/2021
11/10/2020

Locations

Permits

Permit Number: PRBD202003450

Building
Finaled
04/30/2020
05/09/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Partial Pass 5/8/2020 (8:00 - 10:00) 5/8/2020 (AM) 05/08/2020
Framing Progress inspection. A. Need plumbing rough in and fire caulking of floor and ceiling penetrations for 2 hour rating. Ok to Sheetrock one side walls only.
Framing Inspection Partial Pass 5/13/2020 (12:30 - 2:30) 5/13/2020 (PM) 05/13/2020
Wall framing and plumbing floor penetrations fire caulking, - passed. CALL FOR ABOVE CEILING INSPECTIONS FOR - A. Cover above ceiling interior side building perimeter with scrim foil, patch existing fireproofing at areas discussed, provide exit signage to all exits, provide emergency lighting by wall battery packs, or by ceiling lighting wired on the building generator circuit. CALL FOR ABOVE CEILING INSPECTION WHEN READY, PRIOR TO CEILING TILES, FOR ALL TRADE INSPECTIONS, AND THEN FOR BUILDING INSPECTION WHEN READY. SEE CORRECTIONS SENT TO CONTRACTOR.
Corrections:


Miscellaneous/Other
Outstanding
05/13/2020
Call for above ceiling inspection when ready for 1- patching existing spray applied fire proofing at beam/column steel areas, 2- cover areas of wood/paper faced insulation at the exterior perimeter of the building (interior side) above ceiling, with approved scrim foil. 3- install Emergency lighting by battery operated wall packs or ceiling lighting hooked to the building generator circuit ( if using green glass exit signs having no emergency lites. 4- call for above ceiling for all trade inspections-mechanical, fire sprinkler, electrical, low voltage and fire alarm wiring. 5- If providing fire rated glass corridor entry/exit doors with proper code compliant glass.

Framing Inspection Passed 5/26/2020 (12:30 - 2:30) 5/26/2020 (PM) 05/26/2020
Corrections:


Miscellaneous/Other
Comment Only
05/26/2020
Ceiling framing approved.

Building Final Inspection Passed 7/28/2020 (12:30 - 2:30) 7/28/2020 (PM) 07/28/2020
Need minor corrections inspected by fire Marshall. All trades are final approved
Fire Inspection Final Passed 11/10/2020