PRBD202101754
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Building Final Inspection | Pending | |||
Framing Inspection | Partial Pass | 3/26/2021 (2:30 - 3:30) | 3/26/2021 (PM) | 03/29/2021 |
Miscellaneous/Other
Outstanding
03/29/2021
Framing - partial pass only. A. Contractor must print and provide for approved plans on site for all trade inspections. B. 2x6 ceiling rafters installed already are not fire treated lumber, but suggest covering ceiling rafters with gypsum, and adding additional sprinkler heads above per Bloomington fire marshal.
|
||||
Framing Inspection | Not Ready | 4/5/2021 (10:00 - 12:00) | 4/5/2021 (AM) | 04/05/2021 |
Miscellaneous/Other
Carried Forward
04/05/2021
Framing - partial pass only. A. Contractor must print and provide for approved plans on site for all trade inspections. B. 2x6 ceiling rafters installed already are not fire treated lumber, but suggest covering ceiling rafters with gypsum, and adding additional sprinkler heads above per Bloomington fire marshal.
|
||||
Framing Inspection | Partial Pass | 4/6/2021 (12:30 - 2:30) | 4/6/2021 (PM) | 04/06/2021 |
Miscellaneous/Other
Carried Forward
04/06/2021
Framing - partial pass only.
A. Complete screw fasten, all fire treated plywood, into the wood ceiling joists. Screw spacing -
MAXIMUM SPACING 8 INCHES.
B. Contractor must completely cover the top surface and behind large sprinkler pipe top surface, and all 3 perimeter edges, gaps and openings, with 5/8 gypsum and screws.
C. Fire caulk - all small gaps around the 2 sprinkler heads.
D. Also cover with gypsum and fasten the rear most edge perimiter at rear area of suite, with
E. Call for reinspection.
F. Electrical permit required to reinstall exit signs having emergency lighting, and all 2 x 4 ceiling lites.
|
||||
Framing Inspection | Passed | 4/14/2021 (2:30 - 3:30) | 4/14/2021 (PM) | 04/14/2021 |
Miscellaneous/Other
Outstanding
04/06/2021
Framing - partial pass only.
A. Complete screw fasten, all fire treated plywood, into the wood ceiling joists. Screw spacing -
MAXIMUM SPACING 8 INCHES.
B. Contractor must completely cover the top surface and behind large sprinkler pipe top surface, and all 3 perimeter edges, gaps and openings, with 5/8 gypsum and screws.
C. Fire caulk - all small gaps around the 2 sprinkler heads.
D. Also cover with gypsum and fasten the rear most edge perimiter at rear area of suite, with
E. Call for reinspection.
F. Electrical permit required to reinstall exit signs having emergency lighting, and all 2 x 4 ceiling lites.
|
||||
Fire Inspection Final | VOID | 5/19/2021 (10:00 - 12:00) | 5/19/2021 (AM) | 05/19/2021 |
Building Final Inspection | Not Ready | 5/19/2021 (10:00 - 12:00) | 5/19/2021 (AM) | 05/19/2021 |
Miscellaneous/Other
Carried Forward
05/19/2021
Need 2 electrical permits - and one exterior sign permit.
1 electrical permit for store interior above ceiling.
1 electrical permit for new exterior sign.
Need fire marshal final.
Signature on card and permit # not valid or legitimate.
|
||||
Fire Inspection Final | Passed | 5/19/2021 | 05/20/2021 | |
Building Final Inspection | Not Ready | 6/7/2021 (8:00 - 10:00) | 6/7/2021 (AM) | 06/07/2021 |
Building Final Inspection | Passed | 10/13/2021 (8:00 - 10:00) | 10/13/2021 (AM) | 11/04/2021 |