Permit Application Status

PRBD202105164


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRBD202105164
Building
Finaled
GKII NORTHLAND CENTER LLC
Alteration/Repair/Replace
Not Required
Replace finishes throughout lobby and corridor included anew gypsum ceiling at elevator lobby - 3rd Floor Corridor.
05/04/2021
06/01/2021
05/14/2022
11/15/2021

Locations

Permits

Permit Number: PRBD202105164

Building
Finaled
06/01/2021
05/14/2022

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Passed 7/20/2021 (10:00 - 12:00) 7/20/2021 (AM) 07/20/2021
Corrections:


Miscellaneous/Other
Comment Only
07/20/2021
Framing approved contingent on electrical rough in approval.

Building Final Inspection Partial Pass 8/23/2021 (8:00 - 10:00) 8/23/2021 (AM) 08/23/2021
See corrections.
Corrections:


Miscellaneous/Other
Carried Forward
08/23/2021
Elevator remodel. A.No permit card on site. B Work covered with out inspections. C. Electrical ceiling lites - must be rated. Above ceiling inspections for fire sprinkler rough in, and low voltage wiring inspection. D. Remove paint from rated exit door into stairwell. E. Provide exit sign to stairwell with rated door. F. Emergency lighting required to building generator circuit. G. Building permit card must be posted in elevator lobby.

Fire Inspection Final Passed 8/23/2021 (8:00 - 10:00) 8/23/2021 (AM) 08/26/2021
Fire Rated Assemblies Inspection Passed 11/15/2021
Building Final Inspection Passed w/ Conditions 11/15/2021
Final 3rd floor spec suite. Emergency lighting was to be on the building generator circuit.
Corrections:


Miscellaneous/Other
Outstanding
08/23/2021
Elevator remodel. A.No permit card on site. B Work covered with out inspections. C. Electrical ceiling lites - must be rated. Above ceiling inspections for fire sprinkler rough in, and low voltage wiring inspection. D. Remove paint from rated exit door into stairwell. E. Provide exit sign to stairwell with rated door. F. Emergency lighting required to building generator circuit. G. Building permit card must be posted in elevator lobby.