PRBD202106535
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Building Final Inspection | Pending | |||
|
Corrections:
Miscellaneous/Other
Outstanding
09/15/2021
Final - A. Need mechanical final and balance reports for dedicated supply and return air for new classrooms, and other final for new roof top for the existing building. B. Need electrical and plumbing finals for new classrooms. Note special order plumbing sink fixtures are back ordered. C. Fire final alarm system has passed, fire marshal wants 2 exit signs, one for each new classroom.
|
||||
| Framing Inspection | Partial Pass | 7/27/2021 (8:00 - 10:00) | 7/27/2021 (AM) | 07/27/2021 |
| Framing approved. Call for fire caulking of floor/ ceiling assembly. | ||||
| Framing Inspection | Passed | 8/2/2021 (10:00 - 12:00) | 8/2/2021 (AM) | 08/02/2021 |
| Main floor - fire-caulk. Floor ceiling penetrations. Passed. Main floor framing - passed. | ||||
| Building Final Inspection | Partial Pass | 9/15/2021 (10:00 - 12:00) | 9/15/2021 (AM) | 09/15/2021 |
|
Corrections:
Miscellaneous/Other
Outstanding
09/15/2021
Final - A. Need mechanical final and balance reports for dedicated supply and return air for new classrooms, and other final for new roof top for the existing building. B. Need electrical and plumbing finals for new classrooms. Note special order plumbing sink fixtures are back ordered. C. Fire final alarm system has passed, fire marshal wants 2 exit signs, one for each new classroom.
|
||||
| Fire Inspection Final | Issue TCO | 9/15/2021 (10:00 - 12:00) | 9/15/2021 (AM) | 09/21/2021 |
| Fire Inspection Final | Passed | 09/22/2021 | ||