PRBD202111563
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Passed w/ Conditions | 11/5/2021 (10:00 - 12:00) | 11/5/2021 (AM) | 11/05/2021 |
Corrections:
Miscellaneous/Other
Outstanding
11/05/2021
Wall framing - passed. A. Need fire sprinkler rough in when ready. B. Need to patch in drywall above electrical panel, above ceiling at tenant separation wall.
C. Need above ceiling inspections prior to installing ceiling tiles for fire sprinkler, electrical, low voltage wiring, fire alarm wiring, prior to installing ceiling tile.
D. Exit signage with Emergency lighting on the exit signs.
|
||||
Progress Inspection | Passed w/ Conditions | 12/14/2021 (8:00 - 10:00) | 12/14/2021 (AM) | 12/14/2021 |
Need above ceiling inspection for fire sprinkler system with indoor vehicle parking. (Does this need Co2/No2 alarm. SEE MECHANICAL INSPECTOR.) | ||||
Fire Inspection Final | Passed | 12/17/2021 (10:00 - 12:00) | 12/17/2021 (AM) | 12/17/2021 |
Building Final Inspection | Partial Pass | 12/17/2021 (12:30 - 2:30) | 12/17/2021 (PM) | 12/17/2021 |
Corrections:
Miscellaneous/Other
Comment Only
12/17/2021
Above ceiling approved. See outstanding comments for correction.
Approved for temp occupancy, call for final with the exit signs to be installed and viewed for final.
|
||||
Miscellaneous/Other
Carried Forward
12/17/2021
Install exit sign at rear door to delineate rear exit, and lower front exit sign due to bulk head blocking view.
|
||||
Building Final Inspection | Passed | 12/20/2021 (10:00 - 12:00) | 12/20/2021 (AM) | 12/20/2021 |
Corrections:
Miscellaneous/Other
Resolved
12/20/2021
Install exit sign at rear door to delineate rear exit, and lower front exit sign due to bulk head blocking view.
|
||||
Miscellaneous/Other
Comment Only
12/20/2021
Corrections completed. Final for this scope of work and permit approved
|