Summary

PRBD202116325
Building
Expired
BLOOMINGTON HOTEL VENTURE
Alteration/Repair/Replace
Not Required
Framing soffits and 1-2 bedroom units (64 units). Interior framing only - in apartment units.
12/14/2021
12/17/2021
10/30/2023

Locations

Permits

Permit Number: PRBD202116325

Building
Expired
12/17/2021
10/30/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Inspection Final Pending
Building Final Inspection Pending
Framing Inspection Partial Pass 12/29/2021 (8:00 - 10:00) 12/29/2021 (AM) 12/29/2021
Corrections:


Miscellaneous/Other
Comment Only
12/29/2021
Mock up unit #838 only…. Framing of wall bump out for electrical panel. Approved. Also went over fire stops and the requirements there of when doing this conversion change to the units and floors. Mold is definitely present at exterior walls under the windows and around the heating pack. Remediation has not started as of yet. Went over mold issues and rusted studs at the open corridor wall, talked with contractor about cleating a new stud next to studs that show excessive rusted stud to maintain integrity of the wall this will be required as needed.

Framing Inspection Partial Pass 1/6/2022 (10:00 - 12:00) 1/6/2022 (AM) 01/06/2022
Corrections:


Miscellaneous/Other
Comment Only
01/06/2022
Viewed two of the mock up fire stops for the assembly submitted for the plumbing piping in the chase wall of units. Installation as per the assembly approved.

Framing Inspection Partial Pass 1/18/2022 (8:00 - 10:00) 1/18/2022 (AM) 01/18/2022
Corrections:


Miscellaneous/Other
Comment Only
01/18/2022
Fire stop prep for the plumbing piping in units on floors 8&9. Approved

Framing Inspection Partial Pass 2/4/2022 (8:00 - 10:00) 2/4/2022 (AM) 02/04/2022
Corrections:


Miscellaneous/Other
Comment Only
02/04/2022
8th floor Wall framing and ceiling framing of units and fireproofing of the 2 exposed beams… approved See outstanding comments for correction.

Miscellaneous/Other
Comment Only
02/04/2022
Fire stops to be inspected for above ceiling on 8th floor, call for inspection when ready.

Progress Inspection Partial Pass 02/04/2022
Corrections:


Miscellaneous/Other
Comment Only
02/04/2022
Viewed the plumbing chase fire stop prep to units with the exposed chase at floors 10-14. Verbal to contractor to add bracing under the metal plate where loose and they can mix and set the 3M fire stop product. Will re-inspect these with the framing inspection.

Framing Inspection Partial Pass 2/25/2022 (12:30 - 2:30) 2/25/2022 (PM) 02/28/2022
Corrections:


Miscellaneous/Other
Comment Only
02/28/2022
Wall Framing for units on 9th floor… approved, pending the removal of wood backing at the electrical boxes. Contractor to verify with inspector the wood has been removed.

Framing Inspection Partial Pass 3/2/2022 (Afternoon) 3/2/2022 (PM) 03/02/2022
Corrections:


Miscellaneous/Other
Comment Only
03/02/2022
Ceiling Framing and fire stops on 8th floor units approved, pending completion of fire alarm wiring inspection prior to covering. Wall framing in units of 10th floor approved. Trash shaft framing on 8th floor … approved.

Framing Inspection Not Ready 8/19/2022 (10:00 - 12:00) 8/19/2022 (AM) 08/19/2022
Corrections:


Miscellaneous/Other
Carried Forward
08/19/2022
Some patching of rated walls , fire caulking, an taping of seems need to be done in units checked at inspection. Contractor to go through units and complete these issues to have ready for the ceiling framing and above ceiling inspection.

Framing Inspection Partial Pass 8/25/2022 (10:00 - 12:00) 8/25/2022 (AM) 08/25/2022
Corrections:


Miscellaneous/Other
Resolved
08/25/2022
Some patching of rated walls , fire caulking, an taping of seems need to be done in units checked at inspection. Contractor to go through units and complete these issues to have ready for the ceiling framing and above ceiling inspection.

Miscellaneous/Other
Comment Only
08/25/2022
12 floor room approved for final … 1241,1231,1201,1203. Fire inspector verified on this day that the CO2 detection system is active and under system supervision. CO2 detectors are not going to be required in the remaining units while system is in place. Ceiling framing and fire stops that are visible approved from west end hallway up to and including units 1420 &1434. Unit 922 water damaged unit framing and mold removal… approved and ok to reinstall gypsum board.

Progress Inspection Partial Pass 8/31/2022 (10:00 - 12:00) 8/31/2022 (AM) 08/31/2022
Corrections:


Miscellaneous/Other
Comment Only
08/31/2022
Framing inspection of units 1435 & 1427… approved. Final inspection for units listed on 12th floor… 1229,1228,1226,1230,1232,1233,1218,1236,1237,1238,1215,1239,1240,1210,1208,1206, & 1204… approved. Call for inspection of remaking units when ready.

Progress Inspection Partial Pass 09/13/2022
Corrections:


Miscellaneous/Other
Comment Only
09/13/2022
Remaining units on 14th floor are approved for covering… fire stops and fire protection at beams are corrected.

Progress Inspection Partial Pass 10/17/2022
Corrections:


Miscellaneous/Other
Comment Only
10/17/2022
Unit 1010, accessibility completed and unit is approved for turnover and final.

Framing Inspection Partial Pass 10/28/2022
Corrections:


Miscellaneous/Other
Comment Only
10/28/2022
First floor back of house corridor… framing of walls at bathroom and kitchen and furred wall that now covers the dumbwaiter… approved, pending electrical inspection.

Framing Inspection Passed 12/20/2022
Corrections:


Miscellaneous/Other
Comment Only
12/20/2022
Framing of wasps and ceilings in the bathrooms located in the pool area…. Approved.

Progress Inspection Passed 5/3/2023 (12:30 - 2:30) 5/3/2023 (PM) 05/03/2023
Corrections:


Miscellaneous/Other
Comment Only
05/03/2023
Emergency lighting test on generator in elevator lobby on floors 8-14. Dog was area and bike racks , break room , zoom room and assembly use rooms on 1st & 2nd levels.