Summary

PRBD202203164
Building
Finaled
MOAC MALL HOLDINGS LLC
Alteration/Repair/Replace
Not Required
Tenant interior improvements at E350
03/30/2022
04/13/2022
04/05/2023
10/07/2022

Locations

Permits

Permit Number: PRBD202203164

Building
Finaled
04/13/2022
04/05/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Partial Pass 5/12/2022 (8:00 - 10:00) 5/12/2022 (AM) 05/12/2022
Corrections:


Miscellaneous/Other
Comment Only
05/12/2022
Consultation only… approved to one side framed walls. Call for framing and fire stop inspection when ready.

Framing Inspection Partial Pass 06/09/2022
Corrections:


Miscellaneous/Other
Comment Only
06/09/2022
Storefront framing approved, pending the installation of bracing attached to the wall above ceiling and to outer framing of ceiling framing. The mall bulkhead cannot be used as/for support of this ceiling framing.

Building Final Inspection Partial Pass 7/12/2022 (10:00 - 12:00) 7/12/2022 (AM) 07/12/2022
Corrections:


Miscellaneous/Other
Comment Only
07/12/2022
Approved for temp occupancy of this side of the space pending EH approval. Abracadabra wall to be on place for the next phase of this buildout.

Fire Inspection Final Partial Pass 7/12/2022 (10:00 - 12:00) 7/12/2022 (AM) 07/14/2022
Framing Inspection Passed w/ Conditions 8/3/2022 (10:00 - 12:00) 8/3/2022 (AM) 08/03/2022
Corrections:


Miscellaneous/Other
Comment Only
08/03/2022
Framing of interior walls of space approved. See outstanding comments for correction.

Miscellaneous/Other
Comment Only
08/03/2022
The back wall of space is actually the 2hr rated wall of the stairwell. No plumbing or electrical can be installed within that wall, there needs to be a fur wall outside of the rated wall to run these installations into. Contractor cano gain a fire protection engineer assessment of how to fix this wall rating, this assessment must be provided to the city for record retention. Inspection of this wall is required prior to closing up wall.

Progress Inspection Partial Pass 8/31/2022 (10:00 - 12:00) 8/31/2022 (AM) 08/31/2022
Corrections:


Miscellaneous/Other
Carried Forward
08/31/2022
Viewed stair shaft wall in the space remodel. Corrections: 1) cut out gypsum at plumbing penetrations of wall and correct the annular space around the penetrations. 2) install intumescent fire stop pads in electrical boxes. Provide pictures of item number 1 to inspector. Call for inspection of fire stops of all penetrations in this wall section and have intumescent pads in the electrical boxes as well for the inspection.

Fire Inspection Final Passed 9/30/2022 (10:00 - 12:00) 9/30/2022 (AM) 09/30/2022
Building Final Inspection Partial Pass 9/30/2022 (10:00 - 12:00) 9/30/2022 (AM) 09/30/2022
Corrections:


Miscellaneous/Other
Carried Forward
09/30/2022
1) need to verify fire stops at the penetrations of plumbing and electrical at the stair shaft wall. 2) front entry door to be installed to this space. 3) finish cleaning and installation of finishes and doors.

Miscellaneous/Other
Comment Only
09/30/2022
Will approve the use of the finished service rooms and clean rooms only at this time, call for final when ready and completed.

Building Final Inspection Partial Pass 10/5/2022 (7:00 - 8:00) 10/5/2022 (AM) 10/05/2022
Corrections:


Miscellaneous/Other
Carried Forward
10/05/2022
1) need to verify fire stops at the penetrations of plumbing and electrical at the stair shaft wall. 2) front entry door to be installed to this space. 3) finish cleaning and installation of finishes and doors.

Miscellaneous/Other
Comment Only
10/05/2022
Outstanding item number 1 is corrected. Front door to be installed for final of this permit.

Building Final Inspection Passed 10/7/2022 (10:00 - 12:00) 10/7/2022 (AM) 10/07/2022
Corrections:


Miscellaneous/Other
Resolved
10/07/2022
1) need to verify fire stops at the penetrations of plumbing and electrical at the stair shaft wall. 2) front entry door to be installed to this space. 3) finish cleaning and installation of finishes and doors.

Miscellaneous/Other
Comment Only
10/07/2022
Final approved for this space. Note…hang fire extinguisher at wall near cashwrap.