PRBD202214015
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Building Final Inspection | Pending | |||
| Framing Inspection | Partial Pass | 2/1/2023 (8:00 - 10:00) | 2/1/2023 (AM) | 02/01/2023 |
| See Corrections from building framing inspection Feb 1, 2023. | ||||
|
Corrections:
Miscellaneous/Other
Carried Forward
02/01/2023
South demising wall to existing tenant space, A. remove existing fiberglass in roof deck flutes and replace with firmly packed mineral wool insulation.
B. Basement below new tenant space, requires 2 hour fire rated caulk at all floor penetrations, and plumbing floor penetrations.
C. Call for reinspection for all items indicated in one inspection.
D. Framing of interior walls is not completed at this time.
E. Call for reinspection
|
||||
| Above Ceiling Inspection | Passed | 3/9/2023 (8:00 - 10:00) | 3/9/2023 (AM) | 03/09/2023 |
| Fire caulk and mineral wool roof deck flutes. Floor and ceiling penetrations . | ||||
| Building Final Inspection | Not Ready | 5/2/2023 (8:00 - 10:00) | 5/2/2023 (AM) | 05/03/2023 |
| Fire Inspection Final | Passed | 5/24/2023 (8:00 - 10:00) | 5/24/2023 (AM) | 05/24/2023 |
| Building Final Inspection | Partial Pass | 5/24/2023 (8:00 - 10:00) | 5/24/2023 (AM) | 05/24/2023 |
|
Corrections:
Miscellaneous/Other
Outstanding
05/24/2023
A. Parking lot accessible parking spaces. (for existing buildings )
B. Exterior illumination of new branding sign. To bright. Per planning,
C. All outstanding trade finals: (electrical, environmental health )
D. City license for new business.
E. Interior: electrical, plumbing, mechanical. Passed
F. Interior : environmental health passed.
|
||||