PRBD202304543
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Partial Pass | 07/12/2023 | ||
Corrections:
Miscellaneous/Other
Comment Only
07/12/2023
Smoke bulkhead framing at storefront... approved
|
||||
Framing Inspection | Passed | 7/28/2023 (10:00 - 12:00) | 7/28/2023 (AM) | 07/28/2023 |
Corrections:
Miscellaneous/Other
Comment Only
07/28/2023
Interior wall framing, and platform framing... approved
Above ceiling fire proofing and plenum... approved.
Sprinkler work needs to be brought into the rooms below platform and inspected.
|
||||
Fire Inspection Final | Passed | 11/28/2023 (8:00 - 10:00) | 11/28/2023 (AM) | 11/28/2023 |
Inspection canceled by contractor. [Nelson-Thorpe\, Sarah @ 11/15/2023 1:58 PM] | ||||
Building Final Inspection | Failed | 11/28/2023 (8:00 - 10:00) | 11/28/2023 (AM) | 11/28/2023 |
Corrections:
Miscellaneous/Other
Carried Forward
11/28/2023
1) Due to the occupand load and required exits needed, the doors that open in the direction of travel need to be easily identifiable and contrasting in some way. This includes all doors wthin the space used in the path of exiting and the back door to space exit.
2) the storeroom storage cannot have items stored within 18" of ceiling or sprinkler head, a demarcation line for height storage should be marked on walls and storage adjusted to conply.
3) the ladder access in storage needs to have a removable access panel to maintain maintain the collection of heat for the sprinkler head in this room to work properly.
Call in for reinspection of these items for the final occupancy of this space.
|
||||
Miscellaneous/Other
Comment Only
11/28/2023
See outstanding comments for corrections, call for reinspection when items have been corrected.
|
||||
Building Final Inspection | Passed | 11/29/2023 (2:30 - 3:30) | 11/29/2023 (PM) | 11/29/2023 |
Corrections:
Miscellaneous/Other
Resolved
11/29/2023
1) Due to the occupand load and required exits needed, the doors that open in the direction of travel need to be easily identifiable and contrasting in some way. This includes all doors wthin the space used in the path of exiting and the back door to space exit.
2) the storeroom storage cannot have items stored within 18" of ceiling or sprinkler head, a demarcation line for height storage should be marked on walls and storage adjusted to conply.
3) the ladder access in storage needs to have a removable access panel to maintain maintain the collection of heat for the sprinkler head in this room to work properly.
Call in for reinspection of these items for the final occupancy of this space.
|
||||
Miscellaneous/Other
Comment Only
11/29/2023
All doors are now made identifyable, and storage area has been corrected .., Final approved and ok to open.
|