PRBD202314581
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Passed | 1/4/2024 (8:00 - 10:00) | 1/4/2024 (AM) | 01/04/2024 |
Corrections:
Miscellaneous/Other
Comment Only
01/04/2024
Walls, soffit, and storefront framing... approved
Note... wood within storefront framing to be removed and replaced mith metal flat stock.
|
||||
Progress Inspection | Passed | 1/30/2024 (8:00 - 10:00) | 1/30/2024 (AM) | 01/30/2024 |
Corrections:
Miscellaneous/Other
Comment Only
01/30/2024
Above ceiling and ceiling framing.... approved
|
||||
Building Final Inspection | Partial Pass | 3/1/2024 (10:00 - 12:00) | 3/1/2024 (AM) | 03/01/2024 |
Corrections:
Miscellaneous/Other
Carried Forward
03/01/2024
Corrections...
1)Rear exit door to be contrasting from wall color.
2) space to be set up with all fixtures and goods for sale to verift access widths for exiting.
Approved for setup and stocking of space. Call for final when all completed.
|
||||
Fire Inspection Final | Passed | 3/1/2024 (10:00 - 12:00) | 3/1/2024 (AM) | 03/06/2024 |
Building Final Inspection | Not Ready | 3/20/2024 (8:00 - 10:00) | 3/20/2024 (AM) | 03/20/2024 |
Corrections:
Miscellaneous/Other
Resolved
03/20/2024
Corrections...
1)Rear exit door to be contrasting from wall color.
2) space to be set up with all fixtures and goods for sale to verift access widths for exiting.
Approved for setup and stocking of space. Call for final when all completed.
|
||||
Miscellaneous/Other
Carried Forward
03/20/2024
Corrections...
1) shelving and clothing hangers need to be lowered in the sales floor and at store room (if installed) to provide 18" clearance from ceiling.
2) maintain minimum required aisle width in sales floor between racks of clothing. All racks are too close together and cannot allow access for handicap use.
|
||||
Miscellaneous/Other
Comment Only
03/20/2024
Not ready for final inspection, see outstanding comments for corrections and set up final inspection when ready.
Approved to continue to stock only.
|
||||
Building Final Inspection | Passed | 7/2/2024 (10:00 - 12:00) | 7/2/2024 (AM) | 07/02/2024 |
Corrections:
Miscellaneous/Other
Resolved
07/02/2024
Corrections...
1) shelving and clothing hangers need to be lowered in the sales floor and at store room (if installed) to provide 18" clearance from ceiling.
2) maintain minimum required aisle width in sales floor between racks of clothing. All racks are too close together and cannot allow access for handicap use.
|
||||
Miscellaneous/Other
Comment Only
07/02/2024
Final approved
|