PRBD202314643
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Fire Inspection Final | Pending | |||
Framing Inspection | Passed | 3/1/2024 (8:00 - 10:00) | 3/1/2024 (AM) | 03/01/2024 |
Corrections:
Miscellaneous/Other
Comment Only
03/01/2024
All Framing and fire stops... approved
|
||||
Framing Inspection | Passed | 5/6/2024 (8:00 - 10:00) | 5/6/2024 (AM) | 05/06/2024 |
Corrections:
Miscellaneous/Other
Comment Only
05/06/2024
Above ceiling and suspended ceiling framing... approved
|
||||
Building Final Inspection | Partial Pass | 5/24/2024 (2:30 - 3:30) | 5/24/2024 (PM) | 05/24/2024 |
Corrections:
Miscellaneous/Other
Carried Forward
05/24/2024
Corrections....
1) install smoke seal at rear door
2) install escutcheon to sprink head outsie of rear door
3) install fire extinguishers by food cooking area.
4) shelving above prep area in back is to close to ceiling and sprinkler, 18" of clearance needed to ceiling and sprinkler head from any stored goods.
5) label electrical room for fire department requirements.
These items to be checked at final inspection.
|
||||
Miscellaneous/Other
Comment Only
05/24/2024
Approved to set up and train staff.
Call for final when all is completed.
|
||||
Fire Inspection Final | Partial Pass | 5/24/2024 (2:30 - 3:30) | 5/24/2024 (PM) | 05/30/2024 |
Building Final Inspection | Passed | 6/6/2024 (8:00 - 10:00) | 6/6/2024 (AM) | 06/06/2024 |
Corrections:
Miscellaneous/Other
Resolved
06/06/2024
Corrections....
1) install smoke seal at rear door
2) install escutcheon to sprink head outsie of rear door
3) install fire extinguishers by food cooking area.
4) shelving above prep area in back is to close to ceiling and sprinkler, 18" of clearance needed to ceiling and sprinkler head from any stored goods.
5) label electrical room for fire department requirements.
These items to be checked at final inspection.
|
||||
Miscellaneous/Other
Comment Only
06/06/2024
Final for this buildout approved.
|