PRBD202315421
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Building Final Inspection | Pending | |||
| Framing Inspection | Partial Pass | 1/10/2024 (8:00 - 10:00) | 1/10/2024 (AM) | 01/10/2024 |
| Area B per plan. A. consult with contractor on fire caulk areas, origional to building. B. Space was demolitioned. C. Reviewed ( Major) large ductwork origional to building requires fire caulk systems thru origional building masonry wall. D. All new (HVAC diffusers, fire sprinkler supply, and ceiling lighting.) | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
01/10/2024
( Work Area B.) Call for all trade rough in inspections. Framing, Mechanical,
Electrical, low voltage control wiring, fire sprinkler piping, and fire caulk rated
systems. Note- DJ Kranze representitive on site.
|
||||
| Above Ceiling Inspection | Not Ready | 2/15/2024 (10:00 - 12:00) | 2/15/2024 (AM) | 02/15/2024 |
| Cancelled by contractor as sub contractor work not completed, thx. [jsmidt @ 02/15/2024 8:32 AM] | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
02/15/2024
Not ready for inspection. Call when ready.
|
||||
| Above Ceiling Inspection | Passed | 2/20/2024 (10:00 - 12:00) | 2/20/2024 (AM) | 02/20/2024 |
| Above ceiling with contractor. | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
02/20/2024
Above ceiling passed. Verbal order to general contractor to check that all trades have had there above ceiling inspections passed.
|
||||
| Fire Inspection Final | Not Ready | 3/26/2024 (12:30 - 2:30) | 3/26/2024 (PM) | 03/26/2024 |
| Building Final Inspection | Partial Pass | 3/27/2024 (8:00 - 10:00) | 3/27/2024 (AM) | 03/27/2024 |
| Phase 1of 2 passed only. | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
03/27/2024
Final for phase 1 only of 2 phase. Pass for office addition north.
Status, phase 2 to follow.
|
||||
| Framing Inspection | Passed | 3/27/2024 (8:00 - 10:00) | 3/27/2024 (AM) | 03/27/2024 |
| Building final for phase 1 only of 2 phases. Pass phase 1 only. | ||||
|
Corrections:
Miscellaneous/Other
Outstanding
01/10/2024
( Work Area B.) Call for all trade rough in inspections. Framing, Mechanical,
Electrical, low voltage control wiring, fire sprinkler piping, and fire caulk rated
systems. Note- DJ Kranze representitive on site.
|
||||
| Fire Inspection Final | Passed | 04/03/2024 | ||