PRBD202402359
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Progress Inspection | Passed | 12/17/2024 (10:00 - 12:00) | 12/17/2024 (AM) | 12/17/2024 |
|
Corrections:
Miscellaneous/Other
Comment Only
12/17/2024
Last PT deck of level 6...
Columns verifed and as per plans.
Deckis mostly completed and some rebar is still in progress of installation, this deck is subject to third party inspection prior to the moved up early morning deck pour scheduled for 12/18.
|
||||
| Fire Inspection Final | Partial Pass | 7/31/2025 (10:00 - 12:00) | 7/31/2025 (AM) | 07/31/2025 |
|
Corrections:
Miscellaneous/Other
Carried Forward
07/31/2025
Label door for fire alarm control panel, test fire alarm and elevator, gate access for entry (Knox box key switch or opticon), provide exit sign for 2nd floor stair A, install standpipe signs for intermediate standpipe locations, remove outside horn above FDC, add Knox box for access to electrical room and fire alarm control panel. Not for public use until all items completed.
|
||||
| Building Final Inspection | Issue TCO | 07/31/2025 | ||
|
Corrections:
Miscellaneous/Other
Comment Only
07/31/2025
The bulk of the work to this ramp is completed, what remains id.. Signage at parking, bollards, guardrails/handrials at stairways, some exterior finishes, and elevator signoff by the state inspector.
Temporary Occupancy will be granted at this point, but not for public or employee use at this time.
Call for final when all work is completed.
|
||||
| Lighting Inspection | Passed | 10/6/2025 | 10/07/2025 | |
| Building Final Inspection | Issue TCO | 10/24/2025 (10:00 - 12:00) | 10/24/2025 (AM) | 10/24/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
10/24/2025
Approved for temporary occupancy.
Complete the stripping for the motorcycle parking and the small amout left at the exterior finishes and set up final inspection.
|
||||
| Fire Inspection Final | Passed | 10/24/2025 (10:00 - 12:00) | 10/24/2025 (AM) | 10/27/2025 |
|
Corrections:
Miscellaneous/Other
Outstanding
07/31/2025
Label door for fire alarm control panel, test fire alarm and elevator, gate access for entry (Knox box key switch or opticon), provide exit sign for 2nd floor stair A, install standpipe signs for intermediate standpipe locations, remove outside horn above FDC, add Knox box for access to electrical room and fire alarm control panel. Not for public use until all items completed.
|
||||
| Landscaping Inspection | Passed | 10/31/2025 | 10/29/2025 | |
| Building Final Inspection | Issue CO | 10/30/2025 | ||
|
Corrections:
Miscellaneous/Other
Comment Only
10/30/2025
Ramp is completed and meets code requirements. Approved for occupancy.
|
||||