PRBD202500576
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Framing Inspection | Passed | 04/14/2025 | ||
Corrections:
Miscellaneous/Other
Comment Only
04/14/2025
Framing of the fur wall approved to cover. Call for inspection of fire stops at bathroom and any other framing not yet completed.
Leave open any areas where electrical has to be inspected.
|
||||
Building Final Inspection | Partial Pass | 5/22/2025 (10:00 - 12:00) | 5/22/2025 (AM) | 05/22/2025 |
Corrections:
Miscellaneous/Other
Carried Forward
05/22/2025
Corrections...
1) remove exit sign in the back area of sales along column.
2) rear exit door from fitting room area to be contrasting from wall color and labled as emergency exit only... not employees only.
3) install countertops and complete work in space.
4) accessible signage to be installed to fitting room.
5) lockers to be relocated into storage room and not in the exit path to rear door.
Ok to stock and set up space.call for final inspection.
|
||||
Fire Inspection Final | Partial Pass | 5/22/2025 (8:00 - 10:00) | 5/22/2025 (AM) | 06/02/2025 |
Fire Inspection Final | Passed | 6/3/2025 | 06/03/2025 | |
Building Final Inspection | Passed | 6/3/2025 (10:00 - 12:00) | 6/3/2025 (AM) | 06/03/2025 |
Corrections:
Miscellaneous/Other
Resolved
06/03/2025
Corrections...
1) remove exit sign in the back area of sales along column.
2) rear exit door from fitting room area to be contrasting from wall color and labled as emergency exit only... not employees only.
3) install countertops and complete work in space.
4) accessible signage to be installed to fitting room.
5) lockers to be relocated into storage room and not in the exit path to rear door.
Ok to stock and set up space.call for final inspection.
|
||||
Miscellaneous/Other
Comment Only
06/03/2025
Final for this space approved.
|