Summary

PRBD202501458
Building
Permit(s) Issued
1701 AMERICAN BLVD LLC
Alteration/Repair/Replace
Not Required
Minimal demolition, followed by minimal partition construction. Existing ceiling, mechanical, plumbing, and electrical infrastructure to remain unchanged. All interior work.
02/12/2025
03/25/2025
11/16/2025

Locations

Permits

Permit Number: PRBD202501458

Building
Issued
03/25/2025
11/16/2025

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Inspection Final Pending
Building Final Inspection Pending
Framing Inspection Partial Pass 5/6/2025 (12:30 - 2:30) 5/6/2025 (PM) 05/06/2025
Corrections:


Miscellaneous/Other
Comment Only
05/06/2025
This was more of a consultation with contractor to adress the support and stiffness needed for the long free standing wall. Contractor to add 3 stansions to framing of long wall and 1 at the pass through end of the adjoining wall. Call for inspection when installed. Ok to cover the other framed walls that were built and even to one side the long wall.

Framing Inspection Not Ready 5/12/2025 (10:00 - 12:00) 5/12/2025 (AM) 05/12/2025
Corrections:


Miscellaneous/Other
Carried Forward
05/12/2025
The 24' wall and wing wall has to much wobble even with stancions added. Stanscions to be tightened down completely, and structural studs used around the stanscions need to be attached to top and bottom plates as well as fastened to the stansions better. Architect was called and said hed come out and access the issue and come up with a remedy. Leave wall open for reinspection. One side can be covered and fastened.

Framing Inspection Passed 5/20/2025 (8:00 - 10:00) 5/20/2025 (AM) 05/20/2025
Corrections:


Miscellaneous/Other
Resolved
05/20/2025
The 24' wall and wing wall has to much wobble even with stancions added. Stanscions to be tightened down completely, and structural studs used around the stanscions need to be attached to top and bottom plates as well as fastened to the stansions better. Architect was called and said hed come out and access the issue and come up with a remedy. Leave wall open for reinspection. One side can be covered and fastened.

Miscellaneous/Other
Comment Only
05/20/2025
Framing and wall support approved, ok to cover and finish.