PRBD202504250
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Framing Inspection | Passed | 6/11/2025 (8:00 - 10:00) | 6/11/2025 (AM) | 06/11/2025 |
| Building Final Inspection | Issue TCO | 7/21/2025 (10:00 - 12:00) | 7/21/2025 (AM) | 07/21/2025 |
|
Corrections:
Miscellaneous/Other
Carried Forward
07/21/2025
1. Provide protective boot for under counter plumbing in toilet room rooms. Typical five locations. 2. Add one exit sign in lower level corridor as discussed in field. 3. Confirm final fire approval. 4. Confirm with plan review the requirements for ADA compliant counter height in mezzanine level break room. 5. 15 day temporary occupancy approved.
|
||||
| Fire Inspection Final | Partial Pass | 7/21/2025 (10:00 - 12:00) | 7/21/2025 (AM) | 07/22/2025 |
|
Corrections:
Miscellaneous/Other
Carried Forward
07/22/2025
Must install sprinklers in new offices and install exits signs and repair em lights
|
||||
| Fire Inspection Final | Passed | 9/11/2025 (10:00 - 12:00) | 9/11/2025 (AM) | 09/11/2025 |
|
Corrections:
Miscellaneous/Other
Outstanding
07/22/2025
Must install sprinklers in new offices and install exits signs and repair em lights
|
||||
| Building Final Inspection | Passed | 9/11/2025 (10:00 - 12:00) | 9/11/2025 (AM) | 09/11/2025 |
|
Corrections:
Miscellaneous/Other
Resolved
09/11/2025
1. Provide protective boot for under counter plumbing in toilet room rooms. Typical five locations. 2. Add one exit sign in lower level corridor as discussed in field. 3. Confirm final fire approval. 4. Confirm with plan review the requirements for ADA compliant counter height in mezzanine level break room. 5. 15 day temporary occupancy approved.
|
||||
|
Miscellaneous/Other
Comment Only
09/11/2025
Note, complete installation of drain bibs. OK when done.
|
||||