PRBD202505448
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Building Final Inspection | Pending | 8/5/2025 (12:30 - 2:30) | 8/5/2025 (PM) | |
Fire Inspection Final | Pending | 8/5/2025 (12:30 - 2:30) | 8/5/2025 (PM) | |
Corrections:
Miscellaneous/Other
Outstanding
07/23/2025
Repair back exit door to self close and latch, add smoke seal, replace missing trim plate, add stencil for no storage in rear exit, hang fire extinguishers, verify turbo chefs are 3.6 W.
|
||||
Framing Inspection | Passed w/ Conditions | 06/26/2025 | ||
Corrections:
Miscellaneous/Other
Comment Only
06/26/2025
Storefront infill approved.
Kneewalls are approved for framing and can be covered once electrical inspection of those is completed.
|
||||
Fire Inspection Final | Not Ready | 7/18/2025 (10:00 - 12:00) | 7/18/2025 (AM) | 07/18/2025 |
Tested emergency lights. Corrections needed: Divider needed between sprinkler heads by milkshake machine. Missing escutcheons throughout, rear exit door hardware, ceiling tile throughout. | ||||
Building Final Inspection | Partial Pass | 7/21/2025 (10:00 - 12:00) | 7/21/2025 (AM) | 07/21/2025 |
Corrections:
Miscellaneous/Other
Comment Only
07/21/2025
Approved to stock in the front sales area.
This space is not ready for final at this time.
|
||||
Fire Inspection Final | Not Ready | 7/23/2025 (10:00 - 12:00) | 7/23/2025 (AM) | 07/23/2025 |
Corrections:
Miscellaneous/Other
Carried Forward
07/23/2025
Repair back exit door to self close and latch, add smoke seal, replace missing trim plate, add stencil for no storage in rear exit, hang fire extinguishers, verify turbo chefs are 3.6 W.
|