PRBD202505975
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Framing Inspection | Passed | 9/3/2025 (8:00 - 10:00) | 9/3/2025 (AM) | 09/03/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
09/03/2025
Storefront framing approved.
Ok to one side, leave open for electrical and sprinkler inspections.
|
||||
| Progress Inspection | Passed | 9/15/2025 (7:00 - 8:00) | 9/15/2025 (AM) | 09/15/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
09/15/2025
Back of house Wall framing approved
|
||||
| Above Ceiling Inspection | Passed | 9/17/2025 (12:30 - 2:30) | 9/17/2025 (PM) | 09/17/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
09/17/2025
Above ceiling approved
|
||||
| Progress Inspection | Passed | 10/22/2025 | ||
|
Corrections:
Miscellaneous/Other
Outstanding
10/22/2025
Corrections to be completed for permit final...
1) firestop penetration at back of house rated wall.
2) label " No storage" at walls in back of house exit path, and delineate no storage at floor in front of electrical gear (36") depth by width of gear.
3) relocate exit sign on stora side to the sales sid over the pass through door to back od house.
4) provide accessible writing surface at cashwrap. Conferred with PM of the store and they will install a slide out shelf to the cashwrap, that will allow a surface for handicap use. This will meet the intent of the code requirement.
|
||||
|
Miscellaneous/Other
Comment Only
10/22/2025
Approved for stock and store setup.
See outstanding comments for corrections needed with final inspection.
|
||||
| Building Final Inspection | Not Ready | 10/22/2025 (2:30 - 3:30) | 10/22/2025 (PM) | 10/22/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
10/22/2025
Not ready for final or TCO. See today's progress inspection 10/22/25.
|
||||
| Fire Inspection Final | Not Ready | 10/22/2025 (2:30 - 3:30) | 10/22/2025 (PM) | 10/23/2025 |
| Fire Inspection Final | Passed | 10/24/2025 (12:30 - 2:30) | 10/24/2025 (PM) | 10/24/2025 |
| Building Final Inspection | Failed | 10/24/2025 (12:30 - 2:30) | 10/24/2025 (PM) | 10/24/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
10/24/2025
Tennant wants final to open sunday... unfortunately with the amount of stock in boxes that they loaded into the space, it is prohibiting the sight view of all sales area and exiting along with access aisles.
This space should be clear of all boxes and all items should be on shelves or in their perspective place.
Set up final inspection for monday. No opening or final at this time.
|
||||
| Fire Inspection Final | Passed | 10/27/2025 (8:00 - 10:00) | 10/27/2025 (AM) | 10/27/2025 |
| Building Final Inspection | Passed | 10/27/2025 (8:00 - 10:00) | 10/27/2025 (AM) | 10/27/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
10/27/2025
All corrections completed, final for this permit and scope of work approved. Ok to open to public.
|
||||