Permit Application Status

PRBD202508541


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRBD202508541
Building
Finaled
NORTH PAD DEVELOPMENT LLC
Alteration/Repair/Replace
Assembly, general, community halls, libraries, museums, churches
Tenant buildout for the Super Neon Entertainment/Amusement space. Vanilla Shell/Storefront changes under permit - PRBD202507410
07/17/2025
08/12/2025
03/09/2026
09/10/2025

Locations

Permits

Permit Number: PRBD202508541

Building
Finaled
08/12/2025
03/09/2026

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Framing Inspection Passed 8/15/2025 (8:00 - 10:00) 8/15/2025 (AM) 08/15/2025
Corrections:


Miscellaneous/Other
Comment Only
08/15/2025
Wall framing approved

Building Final Inspection Not Ready 9/3/2025 (12:30 - 2:30) 9/3/2025 (PM) 09/03/2025
Corrections:


Miscellaneous/Other
Comment Only
09/03/2025
not ready for final at this time. 1)Electrical inspection needs to take place with final approval. 2) fire inspection to be scheduled as well. 3)Exit doors need to be easily identified and not blend in with the walls. 4) EM lighting to be tested 5) complete installation of any affixed items including cashwrap. Set up reinspection when all is ready.

Fire Inspection Final Failed 9/3/2025 (12:30 - 2:30) 9/3/2025 (PM) 09/04/2025
Corrections:


Miscellaneous/Other
Carried Forward
09/04/2025
Fire alarm must shut down the sound, relay could not be tested as equipment is not setup, many sprinkler heads are still covered with foil, ceiling tiles must be installed, close all open junction boxes, rear door must be self closing and latching, the umbrella area need to be address as they are obstructions to the sprinkler heads above, rear exit door must be better defined, fire extinguishers are required to be spaced at a max of 75 feet of travel distance, rear door must be labeled with suite number?

Fire Inspection Final Passed 9/10/2025 (7:00 - 8:00) 9/10/2025 (AM) 09/10/2025
Corrections:


Miscellaneous/Other
Resolved
09/10/2025
Fire alarm must shut down the sound, relay could not be tested as equipment is not setup, many sprinkler heads are still covered with foil, ceiling tiles must be installed, close all open junction boxes, rear door must be self closing and latching, the umbrella area need to be address as they are obstructions to the sprinkler heads above, rear exit door must be better defined, fire extinguishers are required to be spaced at a max of 75 feet of travel distance, rear door must be labeled with suite number?

Building Final Inspection Passed 9/10/2025 (10:00 - 12:00) 9/10/2025 (AM) 09/10/2025
Corrections:


Miscellaneous/Other
Comment Only
09/10/2025
Final approved. Ok to finish setup and open for public use.