| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Fire Inspection Final | Not Ready | 5/27/2026 (8:00 - 10:00) | 5/27/2026 (AM) | 05/27/2026 |
|
Corrections:
Miscellaneous/Other
Carried Forward
05/27/2026
Must test mag door drop on fire alarm activation, install sprinkler head in electrical room and cover open junction box, replace any missing ceiling tiles, add occupancy load in conference room, move exit sign to above stair B.
|
||||
| Building Final Inspection | Partial Pass | 5/27/2026 (8:00 - 10:00) | 5/27/2026 (AM) | 05/27/2026 |
|
Corrections:
Miscellaneous/Other
Carried Forward
05/27/2026
1) move exit sign at stair B to above the stair door
2) missing sprinkler head in electrical room, missing coverplate as well.
3) mag holds on entry to be tested with fire alarm.
4) install occupancy load sign to training assembly room.
5) install ceiling tiles where missing.
Call for reinspection when ready, schedule fire and building inspectors.
|
||||
| Fire Inspection Final | Passed | 06/05/2026 | ||
|
Corrections:
Miscellaneous/Other
Outstanding
05/27/2026
Must test mag door drop on fire alarm activation, install sprinkler head in electrical room and cover open junction box, replace any missing ceiling tiles, add occupancy load in conference room, move exit sign to above stair B.
|
||||
| Building Final Inspection | Passed | 06/05/2026 | ||
|
Corrections:
Miscellaneous/Other
Resolved
06/05/2026
1) move exit sign at stair B to above the stair door
2) missing sprinkler head in electrical room, missing coverplate as well.
3) mag holds on entry to be tested with fire alarm.
4) install occupancy load sign to training assembly room.
5) install ceiling tiles where missing.
Call for reinspection when ready, schedule fire and building inspectors.
|
||||
|
Miscellaneous/Other
Comment Only
06/05/2026
Corrections completed and verified by fire inspector... approved for final.
|
||||