PREL201700561
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 4/10/2017 (10:00 - 12:00) | 3/6/2017 | 03/06/2017 |
Corrections:
Miscellaneous/Other
Comment Only
03/06/2017
Multiple phase project. Phase one- Wall RI
HCMC installed except for corridors and bathrooms.
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/31/2017 (10:00 - 12:00) | 3/31/2017 | 03/31/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
03/31/2017
Remove all abandoned limited energy cables.
|
||||
Miscellaneous/Other
Carried Forward
03/31/2017
Install GFCI protection for all receptacle outlets within six foot of any sink
|
||||
Miscellaneous/Other
Carried Forward
03/31/2017
Support all existing fire alarm wiring
Any new fire alarm cable installations require separate electrical permit and inspections
|
||||
Miscellaneous/Other
Comment Only
03/31/2017
Above ceiling RI- OK in phase one as marked on plan
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/10/2017 (10:00 - 12:00) | 4/10/2017 | 04/10/2017 |
Corrections:
Miscellaneous/Other
Resolved
04/10/2017
Remove all abandoned limited energy cables.
|
||||
Miscellaneous/Other
Resolved
04/10/2017
Install GFCI protection for all receptacle outlets within six foot of any sink
|
||||
Miscellaneous/Other
Resolved
04/10/2017
Support all existing fire alarm wiring
Any new fire alarm cable installations require separate electrical permit and inspections
|
||||
Miscellaneous/Other
Comment Only
04/10/2017
Phase 1 final OK- corrections have been made.
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/24/2017 (10:00 - 12:00) | 4/24/2017 | 04/24/2017 |
Corrections:
Miscellaneous/Other
Comment Only
04/24/2017
Phased project- phase 1 B complete and ok to occupy
|
||||
Electrical Rough-in Inspection | Partial Pass | 5/11/2017 (8:00 - 10:00) | 5/11/2017 | 05/11/2017 |
wall rough-in | ||||
Corrections:
Miscellaneous/Other
Comment Only
05/11/2017
Wall RI-OK. HCFMC OK @ patient care area
|
||||
Electrical Rough-in Inspection | Passed | 6/13/2017 (12:30 - 2:30) | 6/13/2017 | 06/13/2017 |
Corrections:
Miscellaneous/Other
Comment Only
06/13/2017
Phase 3 ceiling OK
|
||||
Electrical Final Inspection | Passed | 7/11/2017 (8:00 - 10:00) | 7/11/2017 | 07/11/2017 |