PREL201700634


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL201700634
Electrical
Finaled
NORTH PAD DEVELOPMENT LLC
Repair/Replace
Electrical buildout for Thai Express- MOA.
02/16/2017
02/16/2017
01/26/2021
05/12/2018

Locations

Permits

Permit Number: PREL201700634

Electrical
Finaled
02/16/2017
01/26/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 2/21/2017 (10:00 - 12:00) 2/21/2017 02/21/2017
Wall RI (except front knee wall)
Corrections:


Miscellaneous/Other
Comment Only
02/21/2017
RI-walls (except front wall)

Electrical Rough-in Inspection Partial Pass 3/10/2017 (2:30 - 3:30) 3/10/2017 03/10/2017
Corrections:


Miscellaneous/Other
Comment Only
03/10/2017
Routine- site visit only

Electrical Rough-in Inspection Partial Pass 4/6/2017 04/12/2017
RI - front ceiling
Corrections:


Miscellaneous/Other
Outstanding
04/12/2017
RI - front ceiling

Electrical Final Inspection Issue TCO 5/9/2017 (8:00 - 10:00) 5/9/2017 05/09/2017
Corrections:


Miscellaneous/Other
Outstanding
05/09/2017
GFI-protect POS outlets. GFI-protect outlets next to back hood. Install breaker lock-off for soup warmer circuit. Fix lights.

Electrical Final Inspection Partial Pass 5/11/2017 05/11/2017
Install breaker lock-off for soup warmer circuit. Install 30A/3p breaker for water heater.
Electrical Final Inspection Passed 5/12/2017 (10:00 - 12:00) 5/12/2017 05/12/2017
Electrical Rough-in Inspection VOID 09/11/2018